Parameter Descriptions

3.17 Parameters: 16-** Data Read-outs

3.17.1 16-0* General Status
16-00 Control Word
Range:
Function:
0
[0 - 65535 ] View the Control word sent from the frequency
*
converter via the serial communication port in
hex code.
16-01 Reference [Unit]
Range:
0 ReferenceFeed-
[-999999 - 999999
backUnit
ReferenceFeed-
*
backUnit]
16-02 Reference [%]
Range:
Function:
0 %
[-200 - 200
View the total reference. The total reference
*
%]
is the sum of digital, analog, preset, bus,
and freeze references, plus catch-up and
slow-down.
16-03 Status Word
Range:
Function:
0
[0 - 65535 ] View the status word sent from the frequency
*
converter via the serial communication port in
hex code.
16-05 Main Actual Value [%]
Range:
Function:
0 %
[-100 - 100 %] View the 2-byte word sent with the status
*
word to the Bus Master reporting the
main actual value.
16-06 Absolute Position
Range:
0 CustomRea-
[-2000000000 -
doutUnit2
2000000000
*
CustomRea-
doutUnit2]
16-09 Custom Readout
Range:
0 CustomRea-
[0 - 0 Custom-
doutUnit
ReadoutUnit]
*
MG33MJ02
Programming Guide
Function:
View the present
reference value applied
on impulse or analog
basis in the unit
resulting from the
configuration selected in
1-00 Configuration Mode
(Hz, Nm, or RPM).
Function:
This parameter shows the
absolute position. For
information about
configuring the readouts,
see chapter 3.18.5 17-7*
Absolute Position.
Function:
View the value of custom
readout from
parameter 0-30 Unit for User-
Danfoss A/S © Rev. 10/2014 All rights reserved.
16-09 Custom Readout
Range:
3.17.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0 kW
[0 -
Displays motor power in kW. The value shown
*
10000
is calculated based on the actual motor
kW]
voltage and motor current. The value is
filtered, and therefore approx. 1.3 s may pass
from when an input value changes to when
the data readout values change. The
resolution of readout value on fieldbus is in
10 W steps.
16-11 Power [hp]
Range:
Function:
0 hp
[0 -
View the motor power in hp. The value
*
10000 hp]
shown is calculated based on the actual
motor voltage and motor current. The value
is filtered, and therefore approximately 30 ms
may pass from when an input value changes
to when the data readout values change.
16-12 Motor Voltage
Range:
Function:
0 V
[0 - 6000 V] View the motor voltage, a calculated value
*
used for controlling the motor.
16-13 Frequency
Range:
Function:
0 Hz
[0 - 6500 Hz] View the motor frequency, without
*
resonance dampening.
16-14 Motor current
Range:
Function:
0 A
[0 - 10000
View the motor current measured as a mean
*
A]
value, I
. The value is filtered, and thus
RMS
approximately 1.3 s may pass from when an
input value changes to when the data
readout values change.
16-15 Frequency [%]
Range:
Function:
0 %
[-100 -
View a 2-byte word reporting the actual motor
*
100 %]
frequency (without resonance dampening) as a
percentage (scale 0000-4000 Hex) of
parameter 4-19 Max Output Frequency. Set
9-16 PCD Read Configuration index 1 to send it
with the status word instead of the MAV.
Function:
defined Readout to
parameter 0-32 Custom Readout
Max Value
159
3
3