Parameter Descriptions
6.13 Parameters: 16-** Data Read-outs
16-00 Control Word
Range:
Function:
0
[0 - 65535 ] View the Control word sent from the
*
frequency converter via the serial communi-
cation port in hex code.
16-01 Reference [Unit]
Range:
0.000 Reference-
[-999999.000 -
FeedbackUnit
999999.000
*
ReferenceFeed-
backUnit]
16-02 Reference [%]
Range:
Function:
0.0 %
[-200.0 -
View the total reference. The total
*
200.0 %]
reference is the sum of digital, analog,
preset, bus, and freeze references, plus
catch-up and slow-down.
16-03 Status Word
Range:
Function:
0
[0 - 65535 ] View the Status word sent from the frequency
*
converter via the serial communication port in
hex code.
16-05 Main Actual Value [%]
Range:
Function:
0.00 %
[-100.00 - 100.00
View the two-byte word sent with
*
%]
the Status word to the bus Master
reporting the Main Actual Value.
16-09 Custom Readout
Range:
0.00 CustomRea-
[0.00 - 0.00
doutUnit
CustomRea-
*
doutUnit]
6.13.1 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0.00
[0.00 -
Displays motor power in kW. The value
kW
10000.00
shown is calculated on the basis of the
*
kW]
actual motor voltage and motor current.
The value is filtered, and therefore approx.
MG34M302 - VLT
Operating Instructions VLT
Function:
View the present
reference value applied
on impulse or analog
basis in the unit
resulting from the
configuration selected
in 1-00 Configuration
Mode (Hz, Nm or RPM).
Function:
View the value of custom
readout from 0-30 Unit for
User-defined Readout to
0-32 Custom Readout Max
Value
®
is a registered Danfoss trademark/Commercial Compressor
®
CDS302 and CDS303
16-10 Power [kW]
Range:
Function:
30 ms may pass from when an input value
changes to when the data read-out values
change. The resolution of read-out value
on fieldbus is in 10 W steps.
16-11 Power [hp]
Range:
Function:
0.00
[0.00 -
View the motor power in HP. The value
hp
10000.00 hp]
shown is calculated on the basis of the
*
actual motor voltage and motor current.
The value is filtered, and therefore
approximately 30 ms may pass from
when an input value changes to when
the data read-out values change.
16-12 Motor Voltage
Range:
Function:
0.0 V
[0.0 - 6000.0 V] View the motor voltage, a calculated
*
value used for controlling the motor.
16-13 Frequency
Range:
Function:
0.0 Hz
[0.0 - 6500.0 Hz] View the motor frequency, without
*
resonance dampening.
16-14 Motor Current
Range:
Function:
0.00 A
[0.00 -
View the motor current measured as a
*
10000.00 A]
mean value, I
and thus approximately 30 ms may pass
from when an input value changes to
when the data read-out values change.
16-15 Frequency [%]
Range:
Function:
0.00
[-100.00 -
View a two-byte word reporting the
%
100.00 %]
actual motor frequency (without
*
resonance dampening) as a percentage
(scale 0000-4000 Hex) of 4-19 Max Output
Frequency. Set 9-16 PCD Read Configu-
ration index 1 to send it with the Status
Word instead of the MAV.
16-16 Torque [Nm]
Range:
Function:
0.0
[-3000.0 -
View the torque value with sign, applied to
Nm
3000.0
the motor shaft. Linearity is not exact
*
Nm]
between 160% motor current and torque in
relation to the rated torque. Some motors
supply more than 160% torque.
Consequently, the min. value and the max.
value will depend on the max. motor current
. The value is filtered,
RMS
101
6
6