Parameter Descriptions
5-95 Pulse Out #29 Bus Control
Range:
Function:
0 %
[0 - 100
Set the output frequency transferred to output
*
%]
terminal 29 when the terminal is configured as
[45] Bus Controlled in parameter 5-63 Terminal
29 Pulse Output Variable.
This parameter only applies for FC 302.
5-96 Pulse Out #29 Timeout Preset
Range:
Function:
0 %
[0 - 100
Set the output frequency transferred to output
*
%]
terminal 29 when the terminal is configured as
[48] Bus Ctrl Timeout in parameter 5-63 Terminal
29 Pulse Output Variable and a timeout is
detected.
This parameter only applies for FC 302.
5-97 Pulse Out #X30/6 Bus Control
Range:
Function:
0 %
[0 - 100
Set the output frequency transferred to
*
%]
output terminal X30/6 when the terminal is
configured as [45] Bus ctrl. in
parameter 5-66 Terminal X30/6 Pulse Output
Variable.
5-98 Pulse Out #X30/6 Timeout Preset
Range:
Function:
0 %
[0 - 100
Set the output frequency transferred to output
*
%]
terminal X30/6 when the terminal is configured
as [48] Bus Ctrl Timeout in
parameter 5-66 Terminal X30/6 Pulse Output
Variable and a timeout is detected.