Danfoss VLT AutomationDrive FC 302 Programming Manual page 103

Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Parameter Descriptions
5-95 Pulse Out #29 Bus Control
Range:
Function:
0 %
[0 - 100
Set the output frequency transferred to output
*
%]
terminal 29 when the terminal is configured as
[45] Bus Controlled in parameter 5-63 Terminal
29 Pulse Output Variable.
This parameter only applies for FC 302.
5-96 Pulse Out #29 Timeout Preset
Range:
Function:
0 %
[0 - 100
Set the output frequency transferred to output
*
%]
terminal 29 when the terminal is configured as
[48] Bus Ctrl Timeout in parameter 5-63 Terminal
29 Pulse Output Variable and a timeout is
detected.
This parameter only applies for FC 302.
5-97 Pulse Out #X30/6 Bus Control
Range:
Function:
0 %
[0 - 100
Set the output frequency transferred to
*
%]
output terminal X30/6 when the terminal is
configured as [45] Bus ctrl. in
parameter 5-66 Terminal X30/6 Pulse Output
Variable.
5-98 Pulse Out #X30/6 Timeout Preset
Range:
Function:
0 %
[0 - 100
Set the output frequency transferred to output
*
%]
terminal X30/6 when the terminal is configured
as [48] Bus Ctrl Timeout in
parameter 5-66 Terminal X30/6 Pulse Output
Variable and a timeout is detected.
MG33MJ02
Programming Guide
Danfoss A/S © Rev. 10/2014 All rights reserved.
3
3
101

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT AutomationDrive FC 302 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Vlt automationdrive fc 301

Table of Contents

Save PDF