gefran AFE200 4 Series Instruction Manual page 86

Active front end regenerative power supply unit
Table of Contents

Advertisement

1
Done
The parameter displays the Required message when the motor parameters that have
been entered need to be saved. When they have been saved the parameter indicates
Done.
Menu
PAR
Description
4.7
558
Application select
Selection of which IEC 61131-3-compliant application to make operational.
0
None
1
Application 1
2
Application 2
Note!
The Load Default command (par. 580) does not modify this parameter
.
Menu
PAR
Description
4.8
560
Mains voltage
Setting of the available mains voltage value in Volts. Detection of the undervoltage
alarm refers to this value.
0
320 V
1
270 V
2
290 V
3
230 V
4
380V
5
400 V
6
415 V
7
440 V
8
460 V
9
480 V
10
500 V
11
575 V
12
690 V
Menu
PAR
Description
4.9
552
Mains frequency
Setting of the value of the available mains frequency in Hz.
0
50 Hz
1
60 Hz
Menu
PAR
Description
4.10
562
Switching frequency
Setting of the switching frequency value in kHz. The maximum value that can be set
depends on the size of the AFE.
This must not be changed because changing the default setting may affect perform-
ance of the LCL filter.
0
1 kHz
1
2 kHz
2
3 kHz
86
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
AFE200 • Instruction Manual
Def
Min
None
0
Def
Min
400 V
SIZE
Def
Min
50 Hz
0
Def
Min
SIZE
SIZE
Max
Acc
2
ERWZ
Max
Acc
SIZE ERWZS
Max
Acc
1
ERWZS
Max
Acc
SIZE
ERWS

Advertisement

Table of Contents
loading

Table of Contents