gefran AFE200 4 Series Instruction Manual page 105

Active front end regenerative power supply unit
Table of Contents

Advertisement

The value of the voltage output of the function block of the relative analog input is
displayed.
Menu
PAR
Description
9.34
1602
Analog inp 1X type
9.45
1652
Analog inp 2X type
Selection of the type of expansion card input (voltage or current input). Depending on
the input signal, move the switches on the regulation card. Standard inputs are coded
for voltage signals.
0
-10V..+10V
1
0.20mA ... 0.10V
2
4..20mA
Select option 0 in order to connect a maximum voltage of ±12.5V (typically ±10V/5mA)
to the analog input concerned. If the signal is used as a reference, reverse the direc-
tion of rotation of the drive by inverting the voltage polarity.
Select option 1 to connect a max voltage of 12.5V (typically 10V/5mA) or a signal in
current from 0 ... 20 mA to the analog input concerned. The signal must be positive.
Select option 2 to connect a current signal of 4...20 mA to the analog input concerned.
The signal must be positive.
Menu
PAR
Description
9.35
1604
Analog inp 1X scale
9.46
1654
Analog inp 2X scale
Setting of a multiplier factor to apply to the relative analog input of the expansion card.
Example :
The speed reference of a drive is assigned with a max external voltage of 5V.
As the Analog inp X scale parameter the scale factor of 2 is entered (10V : 5V).
Menu
PAR
Description
9.36
1606
An inp 1Xoffset tune
UM
UM
Speed
100%
50%
0
UM
AFE200 • Instruction Manual
Type
FB BIT
Def
ENUM
-10V..+10V
ENUM
-10V..+10V
Type
FB BIT
Def
FLOAT
1.0
FLOAT
1.0
2
1
5V
10V
Type
FB BIT
Def
BIT
0
Min
Max
0
2
0
2
Min
Max
-20.0
20.0
-20.0
20.0
1
Analog inp xX scale = 1,0
Analog inp xX scale = 2,0
2
Min
Max
0
1
Acc
RW
RW
Acc
RW
RW
Acc
RWZ