9.18
1552
Analog inp 2 type
Selection of the type of input (voltage or current). Depending on the input signal, move
the switches on the regulation card. The factory parameter is inputs set for differential
voltage signals (± 10V).
0
-10V..+10V
1
0.20mA ... 0.10V
2
4..20mA
Select option 0 in order to connect a maximum voltage of ±12.5V (typically ±10V/5mA)
to the analog input concerned. If the signal is used as a reference, reverse the direc-
tion of rotation by inverting the voltage polarity.
Select option 1 to connect a max voltage of 12.5V (typically 10V/5mA) or a signal in
current from 0 ... 20 mA to the analog input concerned. The signal must be positive.
Select option 2 to connect a current signal of 4...20 mA to the analog input concerned.
The signal must be positive.
Menu
PAR
Description
9.3
1504
Analog inp 1 scale
9.19
1554
Analog inp 2 scale
Setting of a multiplier factor to apply to the relative analog input.
Example :
The speed reference of a AFE is assigned with a max external voltage of 5V.
As the Analog inp x scale parameter a scale factor of 2 is entered (10V : 5V).
Menu
PAR
Description
9.4
1506
An inp 1 offset tune
9.20
1556
An inp 2 offset tune
Self-tuning command for the relative analog input offset. Automatic fine tuning of the
input. To perform self-tuning, set the input signal to its minimum value and execute
the command. The conditions containing an offset can be compensated. When this
100
UM
Speed
100%
50%
0
UM
AFE200 • Instruction Manual
ENUM
-10V..+10V
Type
FB BIT
Def
FLOAT
1.0
FLOAT
1.0
2
1
5V
10V
Type
FB BIT
Def
BIT
0
BIT
0
0
2
Min
Max
-10.0
10.0
-10.0
10.0
1
Analog inp x scale = 1,0
Analog inp x scale = 2,0
2
Min
Max
0
1
0
1
RW
Acc
RW
RW
Acc
ERW
ERW