gefran AFE200 4 Series Instruction Manual page 137

Active front end regenerative power supply unit
Table of Contents

Advertisement

1 Pwm
2 Pwm&Ctrl
Menu
PAR
Description
14.8.5
5712
FL N Fwd slave chg
There are two possible operation modes.
In the first, the master sends the data frame to the first slave. The first slave takes all
the data in the frame and sends the same frame to the next slave without making any
changes. The same sequence is repeated by all the slave drives.
In the second, the master sends the data frame to the first slave. The first slave takes
all the data in the frame, replaces part of the data and then sends the frame to the
next slave drive. The same sequence is repeated by all the slave drives.
This parameter is ineffective on the master drive.
On the slave drive this parameter is used to configure the amount of data to be re-
placed in the data frame.
FL N Fw slave change
Menu
PAR
Description
14.8.6
5714
FL fault enable src
This parameter is used to select the origin (source) of the FL fault enable signal.
The signal to be associated with this function can be selected from the "L_DIGSEL1"
selection list.
0
FL fault enable not active (No FastLink alarm signal)
1
FL fault enable active (FastLink alarm signal)
When the drive detects a FastLink fault, it prepares to trigger a "FastLink fault" alarm.
This command is used to select whether an alarm is generated when a fault is de-
tected.
Alarm generation is enabled in the default configuration.
The configuration of the "FL fault enable src" parameter can be changed to control
the phases in which alarm generation is enabled.
For example, by connecting the "FL fault enable src" parameter to "Enable state
mon" you can enable generation of the "FastLink fault" alarm in the phase when the
drive is enabled.
In systems where drive the drives are not powered-off simultaneously, some drives
detect a FastLink fault and generate a FastLink alarm.
The Fastlink transfers information between the drives and the function
for synchronising the generation of Pwm signals with the Pwm signals
of the master is enabled. The variables in the 11) Updating times for
the various functions table are synchronised at 125 us
The Fastlink transfers information between the drives, the function for
synchronising the generetion of Pwm signals with the Pwm signals of
the master is enabled and the function for synchronsing control tasks
with the control tasks of the master is enabled. The variables in table
"Updating times for the various functions" (on manual 1S5F32_EXP-
FL-XCAN-ADV) and the MDPLC tasks are also synchronised to 1 ms
and 8 ms.
UM
Type
UINT16
Information replaced
0
1
2
FL Fw 1, FL Fw 2
3
FL Fw 1, FL Fw 2, FL Fw 3
4
FL Fw 1, FL Fw 2, FL Fw 3, FL Fw 4
UM
Type
LINK
L�DIGSEL1
AFE200 • Instruction Manual
FB BIT
Def
0
None
FL Fw 1
FB BIT
Def
16BIT
6002
Min
Max
Acc
0
4
ERWZ
Min
Max
Acc
0
16384 ERW
137