gefran AFE200 4 Series Instruction Manual page 107

Active front end regenerative power supply unit
Table of Contents

Advertisement

Setting of an offset value to algebrically add to the relative analog input of the expan-
sion card.
Menu
PAR
Description
9.40
1616
Analog inp 1X offset
9.51
1666
Analog inp 2X offset
Setting of an offset value to algebrically add to the relative analog input of the expan-
sion card.
Menu
PAR
Description
9.41
1618
Analog inp 1X gain
9.52
1668
Analog inp 2X gain
This parameter contains the value of the multiplier factor to apply to the analog refer-
ence of the expansion card calculated using the Analog inp gain tune function.
Example :
An external analog reference only reaches a maximum of 9.8V instead of 10V. 1.020
(10V : 9.8V) is entered as the Analog inp x gain parameter.
The same result can be achieved using the Analog inp x gain tune function. This pa-
rameter can be selected from the keypad menu. The maximum analog value available
(in this case 9.8V) must be present on the terminal, with positive polarity. Press the
Enter key on the keypad to start analog reference self-tuning.
Menu
PAR
Description
9.42
1626
An inp 1X sign src
9.53
1676
An inp 2X sign src
L�DIGSEL2
Selection of the origin (source) for the signal to be assigned to the relative digital input
for selecting the sign of the relative analog reference signal. The functions that can be
associated with the digital outputs are listed in the "L_DIGSEL2" selection list.
Menu
PAR
Description
9.43
1632
Analog inp 1X dest
9.54
1682
Analog inp 2X dest
UM
Type
cnt
INT16
cnt
INT16
100%
{
Analog inp x offset
0
UM
Type
FLOAT
FLOAT
UM
Type
LINK
LINK
UM
Type
ILINK
ILINK
AFE200 • Instruction Manual
FB BIT
Def
0
0
FB BIT
Def
1.0
1.0
FB BIT
Def
16
6000
16
6000
FB BIT
Def
0
0
Min
Max
Acc
-32768
+32767 ERW
-32768
ERW
+32767
10V
Min
Max
Acc
-20.0
20.0
ERW
-20.0
20.0
ERW
Min
Max
Acc
0
16384 ERW
0
16384 ERW
Min
Max
Acc
0
0
ER
0
0
ER
107