4 - CONFIG DRIVE
Menu
PAR
Description
4.1
550
Save parameters
Any changes to parameter values immediately affect AFE operations, but are not
automatically saved in the permanent memory.
The "Save Parameters" command is used to save current parameter values in the
permanent memory.
Any changes that are not saved will be lost when the AFE is switched off.
To save parameters follow the procedure described in STEP 6 of the Startup wizard.
Menu
PAR
Description
4.2
554
Access mode
With this parameter you can restrict access to advanced configuration.
Easy
0
Expert
1
The Easy mode gives access to a list of parameters that can be used for rapid AFE
commissioning. This type of configuration is suitable for the majority of applications.
Setting the parameter to Expert gives access to all the parameters in the firmware.
This mode allows an extremely high level of customization to be achieved in order to
exploit the potential of the AFE200 to the full.
Menu
PAR
Description
4.3
120
Input inductance
This value must be the sum of line inductance value + LR3-AFE inductance as per
chapter
If units are connected in parallel, the sum is:
L-AFE + LR3-AFE / Number of units in parallel.
Menu
PAR
Description
4.4
458
DC link capacitor
Setting of the value of the DC-link capacitors.
Menu
PAR
Description
4.5
2020
Take parameters
Stores the choke and capacitor settings. This command must be supplied last after
entering the appropriate values of all the parameters listed above. This involves cal-
culating the voltage and current regulator gains. The AFE cannot be started until the
Take parameters command has been set.
Note!
This is not saved permanently. Use the "Save Parameters" command in the DRIVE CONFIG menu to
save in the permanent memory.
Menu
PAR
Description
4.6
2028
Take status
Indication of the status of parameter saving.
0
Required
UM
Type
BIT
UM
Type
ENUM
UM
Type
mH
FLOAT
"5.6 LCL Filters" on page
UM
Type
uF
FLOAT
UM
Type
BIT
UM
Type
ENUM
AFE200 • Instruction Manual
FB BIT
Def
0
FB BIT
Def
Facile
FB BIT
Def
CALCF
51.
FB BIT
Def
SIZE
FB BIT
Def
0
FB BIT
Def
Required
Min
Max
Acc
0
1
RW
Min
Max
Acc
0
1
RW
Min
Max
Acc
0.0
0.0
RWZS
Min
Max
Acc
0.0
0.0
RWZS
Min
Max
Acc
0
1
RWZ
Min
Max
Acc
0
0
85
R