command is sent, An inp x offset tune is automatically selected so that the available
input signal corresponds to the zero value of the variable. Offset tuning can also be
performed with the AFE enabled. Automatic tuning can only be performed if the follow-
ing condition is present:
Automatic tuning can only be performed if the following condition is present:
- Input voltage less than 1V or input current less than 2 mA
Note!
The value that is obtained automatically can be changed manually if necessary, using Analog inp x
offset.
If the voltage setting on the analog input is higher than 1V, the Value too low alarm is
generated.
Menu
PAR
Description
9.5
1508
An inp 1 gain tune
9.21
1558
An inp 2 gain tune
Self-tuning command for the relative analog input gain. Automatic fine tuning of the in-
put. When this command is sent, Analog inp 1 gain x is automatically selected so that
the available input signal corresponds to the maximum value of the variable. Offset
tuning can also be performed with the AFE enabled.
Two conditions are necessary in order to perform automatic tuning:
Note!
If necessary, the value obtained automatically can be changed manually via Analog inp x gain.
To perform self-tuning, set the input signal to its maximum value and execute the com-
mand. A multiplier factor is calculated to apply to the input signal value (not consider-
ing the Analog inp scale parameter) to reach the full scale value.
If the voltage setting on the analog input is less than 1V, the Value too low alarm is
generated.
Menu
PAR
Description
9.6
1510
Analog inp 1 filter
9.22
1560
Analog inp 2 filter
Filter on the measurement of the corresponding analog input. This parameter can be
used to control the response of the analog input and reduce any possible noise and
interference.
Menu
PAR
Description
9.7
1512
Analog inp 1 top
9.23
1562
Analog inp 2 top
Setting of the upper speed reference limit as a function of the voltage (or current) of
the relative analog reference.
UM
Input voltage greater than 1V or input current greater than 2 mA
Positive polarity. The value found is automatically accepted even for negative
polarity.
UM
ms
ms
UM
cnt
cnt
Type
FB BIT
BIT
BIT
Type
FB BIT
FLOAT
FLOAT
Type
FB BIT
INT16
INT16
AFE200 • Instruction Manual
Def
Min
0
0
0
0
Def
Min
10.0
1.0
10.0
1.0
Def
Min
16384
-32768
16384
-32768
Max
Acc
1
RWZ
1
RWZ
Max
Acc
100.0
ERW
100.0
ERW
Max
Acc
ERW
+32767
ERW
+32767
101

Advertisement

Table of Contents
loading

Table of Contents