A 2.4 MS-SL interface cable wiring sizes 900 kW...1 MW
Fit the AFE200 MASTER and SLAVE power supplier inside the electrical panel.
Connect all the power section cables and connect the 2 signal cables for interfac-
ing between the 3 AFE200.
The cable (code 8S860B, x 2) for connecting the AFE200 is one meter long and
has two quick coupling male MDR connectors at the ends.
AFE200-...-SL
(SLAVE 1)
Wiring instructions:
1.
2.
3.
4.
5.
6.
196
AFE200-...-MS
AFE200-...-SL
(SLAVE 2)
J4 connectors
Connect one of the 2 ends of the interface cable to the XSL connector of the
INT-P-ADV-SLAVE (SLAVE 2) card.
Secure the cable using the specific clamp.
Connect the other end of the cable to connector J4 of the INT-SLAVE (2)
card mounted on the INT-P-ADV-MASTER card of the MASTER AFE.
Secure the cable in the relative clamp
Repeat steps 1-2-3-4 for SLAVE 1.
To prevent the interface cables from coming into contact with the power
terminals, fold the excess length of cable inside the SLAVE AFE as shown in
the figure and secure it using the specific cable clamps.
AFE200 • Instruction Manual
8S860B x 2 (1mt)
1.
2.
3.
4.
6.