gefran AFE200 4 Series Instruction Manual page 123

Active front end regenerative power supply unit
Table of Contents

Advertisement

2
Ingr1!=Ingr2
3
Ingr1<Ingr2
4
Inrg1>Ingr2
5
|Ing1|=|Ing2|
6
|Ing1|!=|Ing2|
7
|Ing1|<|Ing2|
8
|Ing1|>|Ing2|
If set to 0 the comparator is not enabled
If set to 1 the comparator output is enabled when the value of Dig compare input 1 is
inside the window resulting from the value of Dig compare input 2 ± the tolerance set
via the Comparator Window.
If set to 2 the comparator output is enabled when the value of Dig compare input 1 is
not inside the window resulting from the value of Dig compare input 2 ± the tolerance
set via the Comparator Window.
If set to 3 the comparator output is enabled when Compare input 1 is less than Com-
pare input 2.
If set to 4 the comparator output is enabled when Compare input 1 is greater than
Compare input 2.
If set to 5 the comparator output is enabled when the value of Dig compare input 1
is inside the window resulting from the absolute value of Dig compare input 2 ± the
tolerance set via the Comparator Window.
If set to 6 the comparator output is enabled when the absolute value of Dig compare
input 1 is not inside the window resulting from the absolute value of Dig compare
input 2 ± the tolerance set via the Comparator Window.
If set to 7 the comparator output is enabled when the absolute value of Dig compare
input 1 is less than the absolute value of Dig compare input 2.
If set to 8 the comparator output is enabled when the absolute value of Dig compare
input 1 is more than the absolute value of Dig compare input 2.
Menu
PAR
Description
13.3.6
3672
Compare window
Setting of the tolerance window for comparing the Dig compare input 1 and Dig
compare input 2 signals.
Menu
PAR
Description
13.3.7
3674
Compare delay
Setting of the delay for signalling the result of the comparison.
Menu
PAR
Description
13.3.8
3676
Compare output
The status of the comparator output is displayed:
0
The result of the set comparison is negative
1
The result of the set comparison is positive
UM
Type
FB BIT
perc
FLOAT
UM
Type
FB BIT
s
FLOAT
UM
Type
FB BIT
BIT
16
AFE200 • Instruction Manual
Def
Min
0.0
0.0
Def
Min
0.0
0.0
Def
Min
0
0
Max
Acc
100.0
ERW
Max
Acc
30.0
ERW
Max
Acc
1
ER
123