gefran AFE200 4 Series Instruction Manual page 152

Active front end regenerative power supply unit
Table of Contents

Advertisement

Menu
PAR
Description
-
4712
Alm dig out mon 3
This signal is activated when the alarm configured in parameter 4704 alarm dig sel 3
is active.
Menu
PAR
Description
-
4714
Alm dig out mon 4
This signal is activated when the alarm configured in parameter 4706 alarm dig sel 4
is active.
Menu
PAR
Description
-
4770
First alarm
This parameter displays the first alarm to be activated.
0
No alarm
1
Overvoltage
2
Undervoltage
3
Ground fault
4
Overcurrent
5
Desaturation
6
MultiUndervolt
7
MultiOvercurr
8
MultiDesat
9
Undervolt AC
10
Overvoltage AC
11
Heatsink OT
12
HeatsinkS OTUT
13
Intakeair OT
14
Drive overload
15
Bres overload
16
Opt Bus fault
17
Opt 1 IO fault
18
Opt 2 IO fault
19
Opt Enc fault
20
External fault
21
Emg stop alarm
22
Power down
23
Prc fbk loss
24
Not Used1
25
Not Used2
26
Not Used3
27
ExtIO fault
28
FastLink fault
29
Not Used6
30
Not Used7
31
Not Used8
32
Not Used9
33
Plc1 fault
34
Plc2 fault
35
Plc3 fault
36
Plc4 fault
37
Plc5 fault
38
Plc6 fault
39
Plc7 fault
40
Plc8 fault
Menu
PAR
Description
-
4780
Alarm PLC
152
UM
Type
FB BIT
BIT
16BIT
UM
Type
FB BIT
BIT
16BIT
UM
Type
FB BIT
UINT32
16BIT
UM
Type
FB BIT
UINT16
AFE200 • Instruction Manual
Def
Min
0
0
Def
Min
0
0
Def
Min
0
0
Def
Min
0
0
Max
Acc
1
ER
Max
Acc
1
ER
Max
Acc
0
ERW
Max
Acc
0
ER