Lc-Afe (Choke + Capacitors) Dimensions, Cable Cross Section And Data - gefran AFE200 4 Series Instruction Manual

Active front end regenerative power supply unit
Table of Contents

Advertisement

5.6.2 LC-AFE (Choke + capacitors) Dimensions, Cable Cross Section and data

D
B
Type
Code
LC-AFE-4-22-HD
S7ALC9M
LC-AFE-4-22-LD
S7ALC41M
LC-AFE-4-45-HD
S7ALC1M
LC-AFE-4-55-HD
S7ALC43M
LC-AFE-4-90-HD
S7ALC7M
LC-AFE-4-110-HD
S7ALC45M
LC-AFE-4-132-HD
S7ALC11M
LC-AFE-4-160-HD
S7ALC13M
LC-AFE-6-160-HD
S7ALC21M
Type
Code
LC-AFE-4-22-HD
S7ALC9M
LC-AFE-4-22-LD
S7ALC41M
LC-AFE-4-45-HD
S7ALC1M
LC-AFE-4-55-HD
S7ALC43M
LC-AFE-4-90-HD
S7ALC7M
LC-AFE-4-110-HD
S7ALC45M
LC-AFE-4-132-HD
S7ALC11M
LC-AFE-4-160-HD
S7ALC13M
LC-AFE-6-160-HD
S7ALC21M
56
LC-AFE-4-22-HD ... LC-AFE-4-45-HD
W1
W
LC-AFE-4-55-HD ... LC-AFE-6-160-HD
d (approximated)
Dissipated power
50 Hz
60 Hz
W
H
(W)
(W)
24
26
192.5
182
106
118
192.5
232
44
49
192.5
220
178
197
260
245
239
263
260
300
222
246
260
300
404
436
310
335
405
433
310
335
366
446
260
270
Choke
Terminals: X1 L1, X1 L2, X1 L3; X2 L1, X2 L2, X2 L3
-5%/+10%
Recommended Cable
Cross Section
(mm
) / AWG/kcmil
2
(µH)
140
16 / 6
470
65
35 / 2
315
205
95 / 4/0
145
145
240 / 500
95
2 x 100 / 2xAWG 4/0
185
95 / AWG 4/0
AFE200 • Instruction Manual
C
B
Dimensions (mm)
d
W1
d1
A
150
125
125
-
245
125
125
-
150
125
125
-
294
200
125
15
286
210
130
10
306
200
125
15
341
250
150
15
341
250
150
15
305
200
125
15
Tightening
Lock screw
torque (min)
diameter
(Nm)
M6
6
M6
6
M8
13
M10
25
M10
25
M10
25
9
Bars
B
C
D
-
-
1 x Ø6
-
-
1 x Ø6
-
-
1 x Ø6
30
3
1 x Ø11
20
3
1 x Ø9
30
3
1 x Ø11
30
4
1 x Ø11
30
5
1 x Ø11
30
5
1 x Ø11
Terminals: X2 L1-1, X2 L2-1, X2 L3-1
Maximum Cable
Recommended
Cross Section
stripping
(mm
/ AWG)
(mm)
2
1.3 / 16
12
1.3 / 16
12
1.3 / 16
12
1.3 / 16
12
1.3 / 16
12
1.3 / 16
12
W
W1
Weight
(kg) ~
10
18
12
27
31
35
40
40
29
Tightening
torque (min)
(Nm)
0.7
0.7
0.7
0.7
0.7
0.7

Advertisement

Table of Contents
loading

Table of Contents