A 2.5 MS-SL interface cable wiring size 1.35 MW

Fit the AFE200 MASTER and SLAVE power supplier inside the electrical panel.
Connect all the power section cables and connect the 3 signal cables for interfac-
ing between the 4 AFE200.
The cables (code 8S860B x 2 + code 8S870B x 1) for connecting the AFE200-...-
SL and AFE200-...-SL2 are respectively one and two meters long and have two
quick coupling male MDR connectors at the ends.
AFE200-...-SL2
(SLAVE 3)
6.
8S870B
Wiring instructions:
1.
2.
3.
4.
5.
6.
8S860B x 2 (1mt)
8S870B x 1 (2mt)
AFE200-...-MS
AFE200-...-SL
(SLAVE 1)
J4 connectors
8S860B
Connect one of the 2 ends of the interface cable to the XSL connector of the
INT-P-ADV-SLAVE (SLAVE 2) card.
Secure the cable using the specific clamp.
Connect the other end of the cable to connector J4 of the INT-SLAVE (2)
card mounted on the INT-P-ADV-MASTER card of the MASTER AFE.
Secure the cable in the relative clamp
Repeat steps 1-2-3-4 for SLAVE 1 and SLAVE 3 (see figures 6-7 for INT-
SLAVE position on the INT-P-ADV-MASTER and wiring)
To prevent the interface cables from coming into contact with the power
terminals, fold the excess length of cable inside the SLAVE AFE as shown in
the figure and secure it using the specific cable clamps.
AFE200 • Instruction Manual
Supplied with AFE200-...-SL
Supplied with AFE200-...-SL2
AFE200-...-SL
(SLAVE 2)
8S860B
1.
2.
3.
4.
7.
197