Precharge Kit; Fuses Internal To The Pre-Charge Kit - gefran AFE200 4 Series Instruction Manual

Active front end regenerative power supply unit
Table of Contents

Advertisement

5.5 Precharge Kit

The pre-charge kit (mandatory) is not included in the AFE200 order code and must
be ordered separately. The purpose of the pre-charge circuit is to charge the volt-
age in the DC section with a specific charging time that depends on the DC Link
capacitance value and pre-charge resistors. AFE200 units must not be connected
to mains without pre-charging.
Parallel connection
Only the AFE200 master have its own pre-charge circuit.
AFE200-...-4
KIT Size
3220...4450
5900...61320
71600...73550
400...710 kW
900 kW...1 MW
AFE200-...-6
KIT Size
71600...73550
400...710 kW
900 kW...1.65 MW
Note !
The dissipated power from Kit is only temporarily and only during the pre-charge phase; therefore, it
does not generate a constant temperature increase.

5.5.1 Fuses internal to the pre-charge kit

The fuses shown are included as standard with the pre-charge kit.
48
Precharge KIT 400Vac Mains
Code
1
S72828
PRE-CHARGE KIT-AFE-22/45-4
1
S728281
PRE-CHARGE KIT-AFE-90/132-4
2
S728282
PRE-CHARGE KIT-AFE-160/710-4
3
S728284 PRE-CHARGE KIT-AFE-900/1650-4
Precharge KIT 690Vac Mains
Code
2
S728283
PRE-CHARGE KIT-AFE-160/710-6
3
S728285
PRE-CHARGE KIT-AFE-900/1650-6
Sizes
AFE200-
3220 ... 61320 -4
71600 ... 73550 -4
1 MW -4
71600 ... 73550 -6
1 MW ...1.65 MW -6
AFE200 • Instruction Manual
Maximum capacity DC-LINK (AFE+Drive)
Model
Maximum capacity DC-LINK (AFE+Drive)
Model
Type
FUSE-PWR-XC38 15A 600V
FUSE-PWR-XC38 25A 600V
FUSE-PWR-XC51 50A 690V
AC input 480V
AC input 400V
15000 µF
21500 µF
29900 µF
43000 µF
185300 µF
266900 µF
370600 µF
533800 µF
AC input 690V
89700 µF
185300 µF
370600 µF
Q.ty
2
2
2
Code
S829B
S823B
S85C23

Advertisement

Table of Contents
loading