gefran AFE200 4 Series Instruction Manual page 127

Active front end regenerative power supply unit
Table of Contents

Advertisement

Menu
PAR
Description
14.2.4
4010
Fieldbus M->S enable
Setting of fieldbus data updating.
0
Disable
1
Enable
If set to 0, the possibility of sending commands and references from the AFE PLC via
the fieldbus is disabled.
If set to 1 the possibility of sending commands and references from the AFE PLC via
the fieldbus is enabled.
Menu
PAR
Description
14.2.5
4012
Fieldbus alarm mode
Setting of the Opt Bus Fault alarm generation mode.
0
Off
1
On
If set to 0 the alarm is only generated if the AFE is enabled.
If set to 1 the alarm is generated even with the AFE disabled.
Menu
PAR
Description
14.2.6
4014
Fieldbus state
The logic status of the fieldbus connection is displayed. The value depends on the
type of bus that is used.
These logic states are displayed if the selected fieldbus is CANopen or RTE:
0
Stop
1
PreOperational
2
Operational
These logic states are displayed if the selected fieldbus is Profibus:
3
Error
4
WaitPRM
5
WaitCFG
6
DataExchange
7
DPError
The following logic states are displayed if the RTE field bus is selected:
8
SAFE OP
9
INIT
Menu
PAR
Description
14.2.7
4398
RTE protocol
The Real Time Ethernet protocol implemented on the expansion card is displayed.
0
None
1
Ethercat
2
EthernetIP
3
GdNet
4
Profinet
5
ModbusTCP
6
Powerlink
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
INT32
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
AFE200 • Instruction Manual
Def
Min
Enable
0
Def
Min
0
0
Def
Min
Stop
0
Def
Min
None
0
Max
Acc
1
ERWZ
Max
Acc
1
ERWZ
Max
Acc
7
R
Max
Acc
6
ER
127