14 - COMMUNICATION
The AFE200 is provided with a standard port (9 pole sub-D connector: XS) for connecting the RS485
serial line used for AFE-PC point-to-point communication (via the GF-eXpress configuration software)
or for the multidrop connection.
The RS485 serial line format is: 8 data bits, no parity and one stop bit.
14.1 - COMMUNICATION/RS485
Menu
PAR
Description
14.1.1
3800
Drive address
Setting of the address to which the AFE responds when connected to the RS485 se-
rial line.
Menu
PAR
Description
14.1.2
3802
Serial baudrate
Setting of the RS485 serial communication speed (Baud Rate).
0
9600
1
19200
2
38400
Menu
PAR
Description
14.1.3
3810
Serial parameter
Setting of the format of the RS485 serial communication data.
0
None,8,1
1
None,8,2
2
Even,8,1
3
Odd,8,1
Menu
PAR
Description
14.1.4
3804
Serial protocol
Setting of the serial communication protocol:
0
Modbus
1
Jbus
Setting to 0 selects the Modbus RTU (Remote Terminal Unit) serial communication
protocol.
Setting to 1 selects the Jbus serial communication protocol. The Jbus protocol is func-
tionally identical to the Modbus, except for the different numbering of addresses: in the
Modbus these start from zero (0000 = 1st address) while in the JBUS they start from
one (0001 = 1st address) and maintain this difference throughout numbering.
Menu
PAR
Description
14.1.5
3806
Serial delay
Setting of the minimum delay between the AFE receiving the last byte and starting
its response. This delay avoids conflicts on the serial line when the RS485 interface
that is used has not been pre-set for automatic Tx/Rx switching. The parameter only
concerns the use of the standard RS485 serial line.
UM
Type
FB BIT
UINT16
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ms
UINT16
AFE200 • Instruction Manual
Def
Min
1
1
Def
Min
38400
0
Def
Min
None,8,1
0
Def
Min
Modbus
0
Def
Min
0
0
Max
Acc
255
ERW
Max
Acc
2
ERW
Max
Acc
3
ERW
Max
Acc
1
ERW
Max
Acc
1000
ERW