gefran AFE200 4 Series Instruction Manual page 37

Active front end regenerative power supply unit
Table of Contents

Advertisement

Terminal
Designation
R21
COM Digital output 2
R24
Digital output 2
5
Analog output 1
6
Analog output 2
C1
COM Analog output
7
Digital input E
8
Digital input 1
9
Digital input 2
10
Digital input 3
11
Digital input 4
12
Digital input 5
C2
COM Digital inputs
C3
0V 24 OUT
S3
+ 24V OUT
Terminal
Designation
R11
COM Digital output 1
R14
Digital output 1
1
Analog input 1
2
3
Analog input 2
4
S1+
+10 V
S1-
- 10V
13
Digital output 3
14
Digital output 4
IS1
PS Digital output
IC1
COM Digital output
IC2
0V 24 EXT
IS2
+ 24V EXT
+24V
maximum ±10% tolerance. The maximum absorption is 1A.
Caution
Table 5.2.3.1: Regulation terminals
Common reference for digital output 2 (Relay 2)
Programmable digital relay output 2 (NO). Default = Drive ready (PAR 1064)
Analog output 1. Default = Null (PAR 6000)
Analog output 2. Default = Null (PAR 6000)
Common reference for analog outputs and ±10V potential voltage reference
Digital input E . Default = Digital input E mon, PAR 1110 (Enable)
Digital input 1 . Default = Precharge fbk src (PAR 4498)
Digital input 2 . Default . Default = Null (PAR 6000)
Digital input 3 . Default . Default = Null (PAR 6000)
Digital input 4 . Default . Default = Null (PAR 6000)
Digital input 5 . Default = Fault reset src (PAR 4500)
Common reference for digital inputs
+24V supply for IO
Reference point for +24V OUT
Strip T1 (bottom)
Common reference for digital output 1 (Relay 1)
Programmable digital relay output 1 (NO).
Default = Precharge Command (PAR 1122)
Programmable / configurable analog differential input.
Signal: terminal 1. Reference: terminal 2.
Default = Multi ref 0 src
Programmable / configurable analog differential input.
Signal: terminal 3. Reference: terminal 4.
Default = Not used
Voltage reference +10V; reference point: C1 terminal
Analog output -10V; reference point: C1 terminal
Digital output 3. Default = Drive OK (PAR 1062)
Digital output 4. Default = Null (PAR 6000)
Digital outputs 3 / 4 power supply
Common reference for digital outputs 3 / 4
Reference for regulation card 24V external supply
External supply of regulation card
voltage, which is used to externally supply the regulation card has to be stabilized and with a
dc
AFE200 • Instruction Manual
Strip T2 (top)
Function
Function
Max
-
250 V
- 30 V
/ 2A
ac
dc
±12,5 V (typical ±10 V / 5 mA)
- voltage (default):
±12,5 V (typical ±10V/5mA)
- current (set by S3 switch):
0...20mA or 4...20mA (setting by
PAR 1848, 15 - ANALOG OUPUTS
menu)
-
5mA @ +24V (+30V max)
5mA @ +24V (+30V max)
5mA @ +24V (+30V max)
5mA @ +24V (+30V max)
5mA @ +24V (+30V max)
5mA @ +24V (+30V max)
-
150 mA
, ±10 %
(Resettable fuse)
-
Max
-
250 V
- 30 V
/ 2A
ac
dc
- voltage (default):
±12,5 V (typical ±10V/1mA)
- current (set by switches S1-S2):
0...20mA or 4...20mA (set by
PAR 1502 or 1552, 14 - ANALOG
INPUTS menu)
+10 V ±1% / 10 mA
-10 V ±1% / 10 mA
+24 V /
20 mA (typ), 40 mA (max)
+24 V /
20 mA (typ), 40 mA (max)
-
-
-
+24V ±10% / 1A
37