Connection Of Fans Power Supply - gefran AFE200 4 Series Instruction Manual

Active front end regenerative power supply unit
Table of Contents

Advertisement

5.1.6 Connection of fans power supply

Sizes
3220 ... 61320
No connection is necessary: the AFE's internal power supply unit powers the fan (+24Vac).
Terminals
U3
1 x 230V (±10%) 50/60Hz,
2.4A (50Hz) - 3.3A (60Hz)
Sizes
71600 ... 72500
Power the internal fan (max 600W) with a single-phase voltage on terminals U3/V3.
400 kW
(1)
500 kW
(1)
U3
(1) For each
3 x 400V (±10%) 50/60Hz,
module.
1.25/1.65Arms ...
3 x 460V (±10%) 60Hz,
Power the internal fan ( 570W @400V, 930W @460V ) with a three-phase voltage on terminals U3/V3/W3.
Terminals
U3
3 x 400V (±10%) 50Hz,
Sizes
3 x 460V (±10%) 60Hz,
73150 ... 73550
Power the internal fan (max 1200W) with a three-phase voltage on terminals U3/V3/W3.
630 kW
(1)
710 kW
(1)
900 kW
(1)
1 MW
(1)
3 x 380...480V (±10%)
(1) For each
1.9 ... 1.7 Arms
module.
Power the internal fan (max 1200W) with a three-phase voltage on terminals U3/V3/W3.
Make sure the sequence of the three-phase fan power supply phases is the same as that shown on
the relative AFE terminals. If not, the air flow will be inadequate to ensure correct cooling..
Caution
Version before 2009/125/CE (ErP regulation)
V3
PE
Ground
Type of fan compliant 2009/125/CE (ErP)
AFE200 starting from S/N 33GD018605
V3
W3
PE
Ground
1.55Arms
Version before 2009/125/CE (ErP regulation)
V3
W3
PE
1,55Arms
or
Ground
1,7Arms
Type of fan compliant 2009/125/CE (ErP)
AFE200 starting from S/N 33GD018605
50/60Hz,
Ground
AFE200 • Instruction Manual
Terminals
31
250V/10A contact
OK fan contact management terminals 31-32:
Closed: Internal fan OK and powered;
Open: Internal fan in over temperature alarm and/or input power supply
not available.
31
250V/2A contact
OK fan contact management terminals 31-32:
Closed: Internal fan OK (also with non-powered fan)
Open: Internal fan in over temperature alarm
31
250V/10A contact
OK fan contact management terminals 31-32:
Closed: Internal fan OK (also with non-powered fan)
Open: Internal fan in over temperature alarm
250V/10A contact
OK inverter fan contact management terminals 31-32:
Closed: Inverter fan OK and powered;
Open: Inverter fan in alarm or not supplied.
32
32
32
35