9.2 Messages

Note !
For more information see
Error message shown on the
display
Fast IO error
Key expiring
Load default
Load def plc
Load par failed
chapter
Sub-code
Condition: may occur at AFE start-up, during card recognition
0000H-0
Fast IO error (Bus synchronisation)
Solution: contact the Gefran technical support centre.
Condition: this may occur at AFE power-on if the incorrect enabling key was inserted for a given
firmware function. At this stage the firmware function can still be used freely, but this time limit is
about to expire.
xxxxH-x
Number of hours for which the function can still be used freely.
Solution: Ask Gefran for the correct key to enable the desired firmware function.
Condition: may occur during loading of the parameter database saved in flash
normally appears in the following conditions: at initial power-on when a new firmware version is
downloaded, when the regulation is installed on a new size, when the region is changed.
If this message is displayed when the AFE is already operating, this means that a problem has oc-
curred in the parameter database saved in Flash.
If this message is displayed, the AFE automatically performs the Load default command.
0001H-1
The database saved is not valid
0002H-2
The database saved is not compatible
0003H-3
The database saved refers to a different size from the current size
0004H-4
The database saved refers to a different region from the current region
Solution: Set the parameters to the value required and perform Save parameter
Condition: may occur during loading of the parameter database saved in the Flash of the Mdplc
application
Normally appears at initial power-on after downloading a new application.
If this message is displayed when the AFE is already operating, this means that a problem has oc-
curred in the parameter database saved in Flash.
If this message appears the AFE restores the default database, i.e. the one that was downloaded.
0001H-1
The database saved is not valid
Solution: Set the parameters to the value required and perform Save parameter
Condition: during transfer of the parameters from the memory of the keypad to the AFE
0H-0
Communication error
0025H-37 The data saved on the keypad are not valid.
No parameter is transferred from the keypad to the AFE
0026H-38 Incompatible AFE series.
No parameter is transferred from the keypad to the AFE
0027H-39 Incompatible software version.
All the parameters present in the memory of the keypad have been transferred to the
AFE. The set of parameters transferred refers to a AFE with a different firmware version;
therefore, certain parameters may not be updated.
0028H-40 Incompatible AFE size.
All the parameters present in the memory of the keypad (excluding those that depend on
the size of the AFE), have been transferred to the AFE. The parameters that depend on
size maintain their original value.
0029H-41 Error during saving of parameters on the AFE.
All the parameters present in the memory of the keypad have been transferred to the
AFE. The transfer of one or more parameters has caused an "out of range" error, or one
or more parameters does not exist. At the end of transfer, one or more parameters may
not have been updated.