gefran AFE200 4 Series Instruction Manual page 110

Active front end regenerative power supply unit
Table of Contents

Advertisement

10 - ANALOG OUTPUTS
On the AFE200 regulation card there are two programmable analog outputs.
Analog output 1 supplies a two-pole +/-10VDC voltage signal, while analog output 2 can be pro-
grammed to obtain a 0-20mA or 4-20mA output signal in current or a signal in two-pole +/-10VDC
voltage, depending on the parameter assigned.
Table: value of the signal of the analog outputs according to the measurement used
PAR
250
280
282
284
286
2388
252
254
270
110
Description
Output current
Active current ref
React curr ref mon
Active current
Reactive current
Active curr noflt
Output voltage
Output frequency
DC link voltage
AFE200 • Instruction Manual
Full scale output
10V = 200% Heavy Duty AFE rated current (this value can be found in
the manual and is defined @400Vac, default switching frequency and
10V = 200% Mains voltage (PAR 560)
10V = 1000Hz
10V = 7000V
40°C)