11.2
Fuses
Protection of the
Use semiconductor fuses with the tripping characteristic aR (VDE 0636-201 / DIN EN
devices
60269-2-1 / HD 630.2.1 54). In the event of a short circuit, these protect the mains rectifier
unit circuit on the input side against complete destruction, in order that it is possible to
repair the device.
Dimension suitable device protection fuses depending on peak current and the maximum
load integral i
1)

11.2.1 BM5030

m Semiconductor fuses aR (device) BM5030, type NH (for CE only)
Bussmann
Siemens
Size

11.2.2 BM5031, BM5032

m Semiconductor fuses aR (device) BM5031; BM5032, type NH (for CE only)
Bussmann
Ferraz Shawmut
Siemens
Size
262
Instruction handbook b maXX 5000
Document No.: 5.09021.16
of 328
2
t
.
off
Device
BM5030
BM5031
BM5032
BM5043
BM5044
BM5173
BM5173
BM519X
BM53XX
Use fuses that fall below the specified cutoff integral (i
Class J: DFJ-15 U
3NC1 415: 15 A, 14x51
00 25A/1000V: 170M2674
40A/1000V: 170M2676
1 40A/660V: 170M3808
63A/660V: 170M3810
Class J: DFJ-25 U for BM5031
000 25A/690V: 6.9 URD 000 PV 025
40A/690V: 6.9 URD 000 PV 040
00 40A/660V: 3NE8 702
3NC1 415: 25 A, 14x51 for BM5031 3NC1 415: 40 A, 14x51 for BM5031
Maximum load integral
550 A²s
1000 A²s
9500 A²s
3000 A²s
88000 A²s
Fuses integrated in the DC link
2
t
) in the operating point.
off
3NC1 420: 20 A, 14x51
32A/1000V: 170M2675
50A/660V: 170M3809
Class J: DFJ-35 U for BM5032
32A/690V: 6.9 URD 000 PV 032
50A/690V: 6.9 URD 000 PV 050
Baumüller Nürnberg GmbH
1)