7.13.2.3 Timing diagram for switching on BM51XX

Power supply 24V
Ready for mains contactor ON
Output signal
Mains contactor ON
Ready for pulse-enable
Output signal
Pulse enable ON
Input signal
Ready for NC
Output signal
Power supply 24V
Ready for main contactor ON
Main contactor ON
Ready for pulse enable
Pulse enable ON
Ready-to-operate for NC
< 10 s
(boot the device)
< 25 s
(offset (10 s), rotating field (5 s) and synchronisation with mains (10 s))
-
X200-1, X200-2 and X2-11, X2-12 are connected with 24V
-
the contact between X2-9, X2-10 is closed
-
the main contactor is enabled, the BM51XX is connected to the three-
phase system
-
the contact between X2-2, X2-3 is closed X2-2, X2-3
-
BM51XX is waiting for a +24V
-
BM51XX sets X2-7 on +24V
-
the signal „power supply ready" is set on the signal bus X300
< 15 s
(pre-charge (10s) and increase DC link voltage
level on X2:20
DC
level
DC
Instruction handbook b maXX 5000
Document No.: 5.09021.16
7
Installation
to the set value (5 s))
4400_0012_rev01_int.xls
DC
149
of 328