11.1
Cabling

11.1.2 Cable device - motor

Device
Cross-section
BM532X
4 x (0.2 to 6 mm²)
(AWG 24 -10)
BM533X
4 x (4 to 16 mm²)
(AWG 20 - 4)
BM537X
4 x (16 to 50 mm²)
(AWG 6 - 0)
1)
Possible cross-section.
Use a shielded Baumüller cable, optical shield covering > 85%, no single-wires.
For UL-compliant machines/systems, UL-certified cabling must be used.
2)
Only using Baumüller cables with this maximum length and Baumüller mains filters, it can be assumed that the threshold limit value of
the EMC product standard EN 61800-3 is complied with.
3)
If n parallel-routed motor cabling is used, then the maximum length must be reduced by a factor of 1/n.
242
Instruction handbook b maXX 5000
Document No.: 5.09021.16
of 328
NOTE
The total parasitic cable capacitance wire/shielding of the motor cables within the
system must not exceed 30 nF. Additional measurements have to be taken (e.g. the
use of DC link filters) in case of cable capacitances higher than 30 nF.
1)
Maximum length
Dependent on the cross-section used:
4 x 1.5 to 2.5 mm² (AWG 16 -12): 100 m
4 x 4 to 25 mm² (AWG 10 -3): 60 m
4 x 35 mm² (AWG 1): 50 m
 4 x 50 mm² (AWG 1/0): 15 m
2) 3)
Connection to device
Flexible cable with wire end ferrule
Flexible cable with wire end ferrule
Flexible cable with/without wire
end ferrule (clamp terminal)
Cable lug max. width: 20 mm
Baumüller Nürnberg GmbH
Motor connector
(clamp terminal)