Danger from
residual energy
DANGER!
Risk of fatal injury from electrical current!
Stored electric charge.
Discharge time of the modular system = discharge time of the device with the longest
DC link discharge time in the modular system.
Refer to
Therefore:
m Do not touch before taking into account the discharge time of the capacitors and
m Heed corresponding notes on the equipment.
m If additional capacitors are connected to the DC link, the DC link discharge can
7.2
Voltage test
DANGER!
Risk of fatal injury from electrical current!
During the routine test of these devices, a voltage test is performed by Baumüller
Nürnberg GmbH in accordance with EN 61800-5-1, Section 5.2.3.2. It is thus unnec-
essary for the customer to do this.
Therefore:
m Subsequent tests of the devices using high voltages may only be performed by
m Disconnect the device from the system during high-voltage testing!
ZElectrical data–
electrically live parts.
take a much longer time. In this case, the necessary waiting period must itself be
determined or a measurement made as to whether the equipment is de-energized.
This discharge time must be posted, together with an IEC 60417-5036 (2002-10)
warning symbol, on a clearly visible location of the control cabinet.
Baumüller Nürnberg GmbH.
as from page 58.
Instruction handbook b maXX 5000