7.3.1

Connection notes: IT-system or grounded phase conductor system with BM50XX

h The shown wire bridge W100 must be removed when operating on an IT-system or
Figure 53:
NOTICE!
The removed wire bridge must not fall into the device.
grounded phase conductor system (Grounded Delta)
Connection to an IT-system or Grounded Delta system
Correct
Instruction handbook b maXX 5000
Document No.: 5.09021.16
7
Installation
False
127
of 328