7.14
Electrical connections
7.14.9 Connection data
Power supply
system
1U1, 1V1, 1W1
PE power supply
system
PE device
DC link
1C1 and 1D1
166
Instruction handbook b maXX 5000
Document No.: 5.09021.16
of 328
NOTE!
Description of BM5030 with safety function
see
ZC.6.1 Connection data of BM5030 with safety function–
NOTE!
To ensure sufficient current load capacity of the connections, adhere to the specified
torques!
Connection
cross section
BM503X-
Max. 25 mm²
XX0X
BM504X
Max. 50 mm²
BM517X
BM519X
BM503X-
Min. 10 mm²
XX0X
BM504X
½ power supply
BM517X
connection cross
section,
BM519X
Min. 16 mm²
BM53XX
Min. 10 mm²
all other
devices
BM519X
BM5030-XX2X-...
Connection
method
Screw terminal
Screw terminal
Cable lug for M10 Min. 30 Nm
Cable lug for M5 Min. 2.2 Nm
Cable lug for M6 Min. 3.0 Nm
Cable lug for M10 Min. 30 Nm
Cable lug for M5 Min. 2.2 Nm
DC link bar
as from page 311.
Torque
Load capacity
Min. 4.0 Nm
Refer to
Max. 4.5 Nm
ZFuses–
page 261
Min. 6.0 Nm
Max. 8.0 Nm
Max. 40 Nm
Max. 3.0 Nm
Max. 4.0 Nm
Max. 40 Nm
Max. 3.0 Nm
Torque
Max load
capacity of the
Min. 2.2 Nm
Max. 3.0 Nm
Min. 4,0 Nm
Max. 4,8 Nm
Baumüller Nürnberg GmbH
as from
-
-
-
bar
130 A
300 A