3.3
Operating conditions
3.3.5

Correction values at changed operating conditions

The correction values of the permitted output power and output current must be multi-
plied, if the devices b maXX 5000 are used at operation conditions with different correc-
tion values.
The following correction values are to be considered if nothing other is specified at the
„Electrical data" of the device:
NOTE!
Baumüller devices that are intended for operation in grounded delta mains or IT
mains may only be operated in those types of mains up to an installation altitude of
2000 m above MSL. At an installation altitude of 2000 m and higher these devices are
to be operated in TN and TT mains. Power supply of this type can be accomplished
by using an isolating transformer with a secondary-side grounded neutral point, for
example.
NOTE!
The temperature of the water cooler or the cold plate temperature must be higher or
equal to the surrounding temperature to prevent condensation.
48
Instruction handbook b maXX 5000
Document No.: 5.09021.16
of 328
Baumüller Nürnberg GmbH