C.6.1 Connection data of BM5030 with safety function
NOTE!
To ensure sufficient current load capacity of the connections, adhere to the specified
torques!
Power supply
BM5030
with 
1U1, 1V1, 1W1
safety
Power supply
function
PE
DC link
BM5030
with 
1C1 and 1D1
safety
function
X101
BM5030
Connection for
additional DC link
capacitance
function
X200 (SELV/PELV)
24 V power supply
Connection
cross section
Max. 25 mm²
Min. 10 mm²
DC link bar
Connection
cross section
Max. 6 mm²
with
safety
Connection
cross section
Max. 1.5 mm²
(2 wire, 2 pin)
BM5030 with Safety Function
Connection
Torque
method
Screw terminal
Min. 4.0 Nm
Max. 4.5 Nm
Cable lug for M5 Min. 2.2 Nm
Max. 3.0 Nm
Torque
Min. 2.2 Nm
Max. 3.0 Nm
Connection
Torque
method
Plug connector,
spring-clamp
connection
Connection
method
Plug connector,
spring-clamp
connection
Instruction handbook b maXX 5000
Document No.: 5.09021.16
Load capacity
Refer to
ZFuses–
from page 261
-
Max load
capacity of the bar
130 A
Load capacity
-
Max. 41 A
Load capacity
Max. 2.0 A
Plug connector max. 16 A
B
311