The notes below must be observed in case you consider UL 508 C.
ZRequired environmental conditions–
n Note the maximum surrounding air temperature.
n Use in a pollution degree 2 environment only.
ZDesign–
on page 81
n Axis units (BM5X23, BM5X26, BM5X27, BM5X28, BM5X31, BM5X32, BM5X33, BM5X34,
BM5X35)are allowed to be used only in combination with mains rectifiers
(BM5031, BM5032, BM5043, BM5044, BM5174).
ZInstallation procedure–
n Internal overload protection operates after exceeding 200 % of the motor full
load.
ZElectrical connections–
n Position of wiring terminals to indicate the proper connections for the power
supply, load, control circuit, and similar devices refer to
Connections of
ZPage 166–
n Note tightening torque values marked for field terminals.
ZRequirements for the connection cables–
n Use 60°/75°copper wires only.
ZRequirements for the motor temperature sensors–
n Drives do not provide motor overtemperature sensing.