Directives And Declarations; Electromagnetic Compatibility - Siemens LOGO! Series Manual

Hide thumbs Also See for LOGO! Series:
Table of Contents

Advertisement

Technical specifications

8.2 Directives and declarations

8.2
Directives and declarations
8.2.1

Electromagnetic compatibility

Introduction
The HMI device fulfills, among other things, the requirements of the EMC law pertaining to
the domestic European market.
EMC-compatible installation of the HMI device
The EMC-compliant installation of the HMI device and the application of interference-proof
cable is the basis for interference-free operation. The "Directives for interference-free
installation of PLCs" and the "PROFIBUS Networks" manual also apply for the installation of
the HMI device.
Pulse-shaped disturbance
The following table shows the electromagnetic compatibility of modules with regard to pulse-
shaped interference. The precondition for electromagnetic compatibility is that the HMI
device meets the specifications and guidelines for electrical installation.
Pulse-shaped disturbance
Electrostatic discharge
in accordance with IEC
61000-4-2
Burst pulses
(high-speed transient
interference)
in accordance with
IEC 61000-4-4
High-power surge pulses in accordance with IEC 61000-4-5, external protective circuit required (refer
to the manual Automation System S7-300, Installation, "Lightning and overvoltage protection"
section)
Asymmetrical coupling
Symmetrical coupling
118
Tested with
Air discharge: 8 kV
Contact discharge: 6 kV
2 kV power supply cable
2 kV signal cable, > 30 m
1 kV signal cable, < 30 m
2 kV power cable
DC voltage with protective elements
2 kV signal/data cable, > 30 m,
with protective elements as required
1 kV power cable
DC voltage with protective elements
1 KV signal cable, > 30 m, with protective elements as
required
Operating Instructions, 04/2012, A5E02421799-03
Degree of
severity
3
3
3
3
Basic Panels