Eib Inputs/Outputs - Siemens LOGO! Series Manual

Hide thumbs Also See for LOGO! Series:
Table of Contents

Advertisement

3.2

EIB inputs/outputs

The application program "20 CO LOGO! 900E02" controls the communication between the
LOGO! and the EIB/KNX bus via the communication module CM EIB/KNX.
By configuring the application program in ETS (EIB Tool Software), the division of the input
and output area of the LOGO! can be defined as a "hardware channel" and as a "virtual
channel" on the EIB/KNX bus.
This characteristic also applies for analog processing.
A communication object is assigned to each "hardware channel" and each "virtual channel"
of LOGO! module.
The real-time clock of LOGO! can be used as a master or slave via the EIB/KNX bus.
The behavior of the communication objects of the communication module CM EIB/KNX,
when the status of the EIB/KNX bus changes, can also be parameterised.
A "virtual input channel" can be used as a bus state; that is, a bus voltage failure can be
reported.
The settings for analog values in LOGO! (Offset, Gain) do not affect the analog values for
the CM EIB/KNX communication module (the output values of the CM EIB/KNX are always
the raw values between 0 and 1000). In this case, you must parameterize customizing in the
ETS.
Functions of the application program
● Specification of the hardware configuration (number of local digital inputs and outputs,
● Selection of time master or slave
● Use of I24 as a bus status signal
● Behavior on bus voltage failure/recovery
● Input type as monoflop/normal for digital inputs via the EIB/KNX
● Output type as normal/dimmer/edge evaluation for digital outputs via the EIB/KNX
● Data type, adaptation, cyclical sending and sending on change in value for analog
Any further details about configuring the application program in ETS can be found in the
current application program description.
For the application program see Siemens product database from version J onwards:
● http://www.siemens.de/gamma
● http://www.siemens.de/logo
LOGO!
Manual, 04/2011, A5E03556174-01
analog inputs)
outputs via the EIB/KNX and analog inputs on LOGO!
Programming LOGO!
3.2 EIB inputs/outputs
73

Advertisement

Table of Contents
loading

This manual is also suitable for:

Logo! basicLogo! pure

Table of Contents