A.2
Technical data: LOGO! 230...
Power supply
Input voltage
Permissible range
Permissible mains frequency
Power consumption
•
•
•
•
Voltage failure buffering
•
•
Power loss at
•
•
•
•
Backup of the real-time clock at 25
°C
Accuracy of the real-time clock
Digital inputs
Number
Electrical isolation
Number of high speed inputs
Input frequency
•
•
Max. continuous permissible
voltage
Input voltage L1
•
•
•
•
LOGO!
Manual, 04/2011, A5E03556174-01
115 V AC
240 V AC
115 V DC
240 V DC
115 V AC/DC
240 V AC/DC
115 V AC
240 V AC
115 V DC
240 V DC
Normal input
High speed input
Signal 0
Signal 1
Signal 0
Signal 1
LOGO! 230RC
LOGO! 230RCo
115 ... 240 V AC/DC
85 ... 265 V AC
100 ... 253 V DC
47 ... 63 Hz
15 ... 40 mA
•
15 ... 25 mA
•
10 ... 25 mA
•
6 ... 15 mA
•
typ. 10 ms
•
typ. 20 ms
•
1.7 ... 4.6 W
•
3.6 ... 6.0 W
•
1.1... 2.9 W
•
1.4 ... 3.6 W
•
typ. 80 hours without battery
card
typ. 2 years with battery card
typ. ± 2 s / day
8
No
0
max. 4 Hz
•
- -
•
265 V AC
253 V DC
< 40 V AC
•
> 79 V AC
•
< 30 V DC
•
> 79 V DC
•
Technical data
A.2 Technical data: LOGO! 230...
LOGO! 230RCE
115 ... 240 V AC/DC
85 ... 265 V AC
100 ... 253 V DC
47 ... 63 Hz
15 ... 40 mA
•
15 ... 25 mA
•
10 ... 25 mA
•
6 ... 15 mA
•
typ. 10 ms
•
typ. 20 ms
•
1.7 ... 4.6 W
•
3.6 ... 6.0 W
•
1.1 ... 2.9 W
•
1.4 ... 3.6 W
•
typ. 20 days
typ. ± 2 s / day
8
No
0
max. 4 Hz
•
- -
•
265 V AC
253 V DC
< 40 V AC
•
> 79 V AC
•
< 30 V DC
•
> 79 V DC
•
321