8.4 Specifications
8.4.5.2

Conditions of use

Mechanical and climatic conditions of use
The HMI device is designed for use in a location protected from the effects of the weather.
The conditions of use are compliant with requirements to DIN IEC 60721-3-3:
● Class 3M3 (mechanical requirements)
● Class 3K3 (climatic requirements)
Use with additional measures
The HMI device should not be used at the following locations unless additional measures are
taken:
● In locations with a high degree of ionizing radiation
● In locations with difficult operating conditions - for example due to:
● In plants that require special monitoring - for example:
Mechanical ambient conditions
The mechanical ambient conditions for the HMI device are specified in the following table in
terms of sinusoidal vibration.
Frequency range in Hz
10 ≤ f ≤ 58
58 ≤ f ≤ 150
Reducing vibrations
If the HMI device is subjected to greater shocks or vibrations, you must take appropriate
measures to reduce acceleration or amplitudes.
We recommend fitting the HMI device to vibration-absorbent material (on metal shock
absorbers, for example).
138
– Corrosive vapors, gases, oils or chemicals
– Electrical or magnetic fields of high intensity
– Elevators
– Systems in especially hazardous rooms
Constant
Amplitude 0.0375 mm
Constant acceleration 0.5 g
Occasional
Amplitude 0.075 mm
Constant acceleration 1 g