Testing mechanical ambient conditions
The following table provides information on the type and scope of tests for mechanical
ambient conditions.
Tested for
Vibrations
Shock
Climatic ambient conditions
The following table shows the climatic ambient conditions for operation of the HMI device.
Ambient conditions
Temperature
Relative humidity
Atmospheric pressure
Pollutant concentration
Basic Panels
Operating Instructions, 04/2012, A5E02421799-03
Test standard
Vibration test in accordance
with IEC 60068, part 2–6
(sinusoidal)
Shock test in accordance
with IEC 60068, Part 2 –27
Vertical mounting
Mounting at an angle
Comments
Type of vibration:
Transitional rate of the frequency:
1 octave/minute.
10 Hz ≤ f ≤ 58 Hz,
constant amplitude of 0.075 mm
58 Hz ≤ f ≤ 150 Hz,
constant acceleration 1 g
Vibration duration:
10 frequency cycles per axis at each of the three
associated vertical axes
Type of shock: Half-sine
Shock intensity:
Peak value 15 g, duration 11 ms
Direction of impact:
3 shocks in ± direction at each one of the three
associated vertical axes
Permitted range
From 0 to 50° C
From 0 to 40° C
10 to 90 %, without condensation
1080 to 795 hPa
SO
: < 0.5 ppm;
2
Relative humidity < 60%, no
condensation
H
S: < 0.1 ppm;
2
Relative humidity < 60%, no
condensation
Technical specifications
8.4 Specifications
Comments
Slope angle max. 35°
Corresponds to an elevation of –
1,000 to 2,000 m
Test: 10 cm
/m
; 10 days
3
3
Test: 1 cm
/m
; 10 days
3
3
139