Siemens LOGO! Series Manual page 335

Hide thumbs Also See for LOGO! Series:
Table of Contents

Advertisement

Input current at
Delay time at
Line length (unshielded)
Analog inputs
Number
Range
Cycle time for analog value
generation
Line length (shielded and
twisted)
Error limit
Digital outputs
Number
Output type
Electrical isolation
In groups of
Control of a digital input
Continuous current I
terminal)
Surge current
Incandescent lamp load
(25000 switching cycles) at
Fluorescent tubes with
ballast (25000 switching
cycles)
Fluorescent tubes,
conventionally compensated
(25000 switching cycles)
Fluorescent tubes,
uncompensated (25000
switching cycles)
Derating
Short circuit-proof cos 1
LOGO!
Manual, 04/2011, A5E03556174-01
Signal 0
Signal 1
0 to 1
1 to 0
th (per
A.8 Technical data: LOGO! 12/24... LOGO! DM8 12/24R
LOGO! 12/24RC
LOGO! 12/24RCo
LOGO! 12/24RCE
< 0.85 mA (I3...I6)
< 0.05 mA (I1, I2, I7, I8)
> 1.5 mA (I3... I6)
> 0.1 mA (I1, I2, I7, I8)
typ. 1.5 ms
<1.0 ms (I3 ... I6)
typ. 1.5 ms
<1.0 ms (I3 ... I6)
max. 100 m
4 (I1=AI3, I2=AI4, I7=AI1, I8=AI2)
0 ... 10 V DC
input impedance 72 kΩ
300 ms
max. 10 m
± 1.5 % at FS
4
Relay outputs
Yes
1
Yes
max. 10 A per relay
max. 30 A
1000 W
10 x 58 W
1 x 58 W
10 x 58 W
none; across the entire temperature
range
Power protection B16, 600A
Technical data
LOGO! DM8 12/24R
< 0.85 mA
> 1.5 mA
typ. 1.5 ms
typ. 1.5 ms
max. 100 m
- -
- -
- -
- -
- -
4
Relay outputs
Yes
1
Yes
max. 5 A per relay
max. 30 A
1000 W
10 x 58 W
1 x 58 W
10 x 58 W
none; across the entire
temperature range
Power protection B16, 600A