Commissioning a project
6.7 OS update - Basic Panel PN
6.7.4

Updating the operating system using ProSave

Requirements
● The HMI device is connected to a PC on which ProSave is installed.
● The data channel is configured on the HMI device.
Procedure
Proceed as follows:
1. Go to the Windows Start menu and start ProSave on the PC.
2. Select the HMI device type in the "General" tab.
3. Select the type of connection between the HMI device and the PC.
4. Set the connection parameters.
5. Select the "OS Update" tab.
6. Select the HMI device image file "*.img" under "Image path".
7. Switch into "Transfer" mode on the HMI device.
8. Select "Update OS" n the PC to run the operating system update.
9. Follow the instructions in ProSave.
Result
A message is displayed when the operating system update is successfully completed.
The HMI device no longer contains any project data.
108
WinCC flexible: The HMI device image files are available under "WinCC flexible Images"
in the WinCC flexible installation folder or on the installation CD.
WinCC: The HMI device image files are available under "Programme\Automation\Portal
V11\Data\Hmi\Transfer\11.0\Images".
The output area provides information on the version of the successfully opened HMI
device image file.
If you have activated automatic transfer mode for the HMI device, the device
automatically switches to "Transfer" mode when an update is initiated.
A progress bar indicates the progress of the operating system update.
Operating Instructions, 04/2012, A5E02421799-03