Requirements
● The HMI device is connected to a configuring PC.
● No project is open in WinCC flexible.
● When updating the operating system without reset to factory setting only:
Procedure
Proceed as follows:
1. When updating the operating system with reset to factory setting only:
2. On the configuring PC, select the "Communication settings" command in the menu
3. Select the type of HMI device.
4. Select the type of connection between the HMI device and the configuring PC, then set
5. Close the dialog box with "OK".
6. Select the "OS Update" command from the "Project > Transfer" menu in WinCC flexible.
7. Select whether to update the operating system with or without restoring the factory
8. Select the HMI device image file "*.img" under "Image path".
9. When updating without reset to the factory settings only:
10. In WinCC flexible, select "Update OS" on the configuring PC to run the operating system
11. When updating with reset to the factory settings only:
12. Follow the instructions in WinCC flexible.
Result
A message is displayed when the operating system update is successfully completed.
The HMI device no longer contains any project data.
Basic Panels
Operating Instructions, 04/2012, A5E02421799-03
The data channel is configured on the HMI device.
Switch off power to the HMI device.
"Project > Transfer" in WinCC flexible.
The "Communication Settings" dialog opens.
the connection parameters.
settings by setting the "Reset to factory settings" check box accordingly.
The HMI device image files are available under "WinCC flexible Images" in the
WinCC flexible installation folder or on the WinCC flexible installation DVD.
The output area provides information on the version of the successfully opened HMI
device image file.
Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when an update is initiated.
update.
Switch on the power supply to the HMI device.
A progress bar indicates the progress of the operating system update.
Commissioning a project