Technical data
A.2 Technical data: LOGO! 230...
Input current at
Delay time at 0 to 1:
Delay time at 1 to 0:
Line length (unshielded)
Digital outputs
Number
Output type
Electrical isolation
In groups of
Control of a digital input
Continuous current I
Surge current
Incandescent lamp load (25000
switching cycles) at
Fluorescent tubes with ballast
(25000 switching cycles)
Fluorescent tubes, conventionally
compensated (25000 switching
cycles)
Fluorescent tubes, uncompensated
(25000 switching cycles)
Short circuit-proof cos 1
Short circuit-proof cos 0.5 to 0.7
Derating
Parallel output circuits for power
increase
322
Signal 0
Signal 1
Signal 0
Signal 1
120V AC
240 V AC
120 V DC
240V DC
120V AC
240 V AC
120 V DC
240V DC
th
230/240 V AC
115/120 V AC
LOGO! 230RC
LOGO! 230RCo
< 0.03 mA AC
> 0.08 mA AC
< 0.03 mA DC
> 0.12 mA DC
typ. 50 ms
typ. 30 ms
typ. 25 ms
typ. 15 ms
typ. 65 ms
typ. 105 ms
typ. 95 ms
typ. 125 ms
max. 100 m
4
Relay outputs
Yes
1
Yes
max. 10 A per relay
max. 30 A
1000 W
500 W
10 x 58 W (at 230/240 V AC)
1 x 58 W (at 230/240 V AC)
10 x 58 W (at 230/240 V AC)
Power protection B16, 600A
Power protection B16, 900A
none; across the entire
temperature range
Not permitted
LOGO! 230RCE
< 0.03 mA AC
> 0.08 mA AC
< 0.03 mA DC
> 0.12 mA DC
typ. 50 ms
typ. 30 ms
typ. 25 ms
typ. 15 ms
typ. 65 ms
typ. 105 ms
typ. 95 ms
typ. 125 ms
max. 100 m
4
Relay outputs
Yes
1
Yes
max. 10 A per relay
max. 30 A
1000 W
500 W
10 x 58 W (at 230/240 V AC)
1 x 58 W (at 230/240 V AC)
10 x 58 W (at 230/240 V AC)
Power protection B16, 600A
Power protection B16, 900A
none; across the entire
temperature range
Not permitted
Manual, 04/2011, A5E03556174-01