Technical data
A.2 Technical data: LOGO! 230...
Input current at
•
•
•
•
Delay time at 0 to 1:
•
•
•
•
Delay time at 1 to 0:
•
•
•
•
Line length (unshielded)
Digital outputs
Number
Output type
Electrical isolation
In groups of
Control of a digital input
Continuous current I
Surge current
Incandescent lamp load (25000
switching cycles) at
•
•
Fluorescent tubes with ballast
(25000 switching cycles)
Fluorescent tubes, conventionally
compensated (25000 switching
cycles)
Fluorescent tubes, uncompensated
(25000 switching cycles)
Short circuit-proof cos 1
Short circuit-proof cos 0.5 to 0.7
Derating
Parallel output circuits for power
increase
322
Signal 0
Signal 1
Signal 0
Signal 1
120V AC
240 V AC
120 V DC
240V DC
120V AC
240 V AC
120 V DC
240V DC
th
230/240 V AC
115/120 V AC
LOGO! 230RC
LOGO! 230RCo
< 0.03 mA AC
•
> 0.08 mA AC
•
< 0.03 mA DC
•
> 0.12 mA DC
•
typ. 50 ms
•
typ. 30 ms
•
typ. 25 ms
•
typ. 15 ms
•
typ. 65 ms
•
typ. 105 ms
•
typ. 95 ms
•
typ. 125 ms
•
max. 100 m
4
Relay outputs
Yes
1
Yes
max. 10 A per relay
max. 30 A
1000 W
•
500 W
•
10 x 58 W (at 230/240 V AC)
1 x 58 W (at 230/240 V AC)
10 x 58 W (at 230/240 V AC)
Power protection B16, 600A
Power protection B16, 900A
none; across the entire
temperature range
Not permitted
LOGO! 230RCE
< 0.03 mA AC
•
> 0.08 mA AC
•
< 0.03 mA DC
•
> 0.12 mA DC
•
typ. 50 ms
•
typ. 30 ms
•
typ. 25 ms
•
typ. 15 ms
•
typ. 65 ms
•
typ. 105 ms
•
typ. 95 ms
•
typ. 125 ms
•
max. 100 m
4
Relay outputs
Yes
1
Yes
max. 10 A per relay
max. 30 A
1000 W
•
500 W
•
10 x 58 W (at 230/240 V AC)
1 x 58 W (at 230/240 V AC)
10 x 58 W (at 230/240 V AC)
Power protection B16, 600A
Power protection B16, 900A
none; across the entire
temperature range
Not permitted
Manual, 04/2011, A5E03556174-01
LOGO!