Parameter Descriptions
0-12 This Set-up Linked to
Option:
4
4
26
VLT® AutomationDrive FC 361
Function:
To enable conflict-free changes
from 1 set-up to another during
operation, link set-ups containing
parameters which are not
changeable during operation. The
link ensures synchronizing of the
not changeable during operation-
parameter values when moving
from 1 set-up to another during
operation. Not changeable during
operation-parameters can be
identified by the label FALSE in the
parameter lists in
chapter 5 Parameter Lists.
Parameter 0-12 This Set-up Linked to
is used by [9] Multi set-up in
parameter 0-10 Active Set-up. Multi
set-up is used to move from 1 set-
up to another during operation
(that is while the motor is running).
Example:
Use multi set-up to shift from set-
up 1 to set-up 2 while the motor is
running. Program in set-up 1 first,
then ensure that set-up 1 and set-
up 2 are synchronized (or linked).
Synchronization can be performed
in 2 ways:
1. Select the following options:
[2] Set-up 2 in
parameter 0-11 Edit Set-up.
[1] Set-up 1 in
parameter 0-12 This Set-up
Linked to.
This starts the linking (synchro-
nizing) process.
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
0-12 This Set-up Linked to
Illustration 4.2 Set-up 1
OR
2. While still in set-up 1, copy set-
up 1 to set-up 2. Then set
parameter 0-12 This Set-up Linked to
to [2] Set-up 2. This starts the
linking process.
Danfoss A/S © 03/2019 All rights reserved.
0-12 This Set-up Linked to
Option:
Function:
0 RPM
Set-up Handling
0-12 This Set-up Linked to
[2]
Illustration 4.3 Set-up 2
When completed,
parameter 0-13 Readout: Linked Set-
ups reads {1,2} to indicate that all
not changeable during operation-
parameters are now the same in
set-up 1 and set-up 2. If there are
changes to a not changeable during
operation parameter, for example
parameter 1-30 Stator Resistance (Rs),
in set-up 2, they are also changed
automatically in set-up 1. A switch
between set-up 1 and set-up 2
during operation is now possible.
[0]
Not linked
*
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
Range:
Function:
0
[0 - 255 ]
View a list of all the set-ups linked
*
by parameter 0-12 This Set-up Linked
to. The parameter has 1 index for
each parameter set-up. The value
for each index shows which set-ups
are linked to that parameter set-up.
Index
0
1
2
3
4
Table 4.1 Set-up Link Example
0.00A
1(1)
0-1*
Setup 2
LCP value
{0}
{1,2}
{1,2}
{3}
{4}
MG06J202