Danfoss VLT AutomationDrive FC 361 Programming Manual page 39

90–315 kw, enclosure sizes j8–j9
Hide thumbs Also See for VLT AutomationDrive FC 361:
Table of Contents

Advertisement

Parameter Descriptions
P 1-33
P 1-30
I
1
X
R
s
U
1
P 1-36
R
Fe
Illustration 4.5 Motor Equivalent Diagram of an Asynchronous
Motor
1-30 Stator Resistance (Rs)
Range:
Function:
Size
[ 0.0140 -
Set the line-to-common stator
related
140.0000
resistance value. Enter the value
*
Ohm]
from a motor datasheet or perform
an AMA on a cold motor.
NOTICE
For salient PM motors:
AMA is not available.
If only line-line data is
available, divide the line-line
value by 2 to achieve the line-
to-common (star point) value.
Alternatively, measure the
value with an ohmmeter. This
also takes the resistance of the
cable into account. Divide the
measured value by 2 and enter
the result.
NOTICE
The parameter value is
updated after each torque
calibration if option [3] 1st
start with store or option [4]
Every start with store is
selected in
parameter 1-47 Torque
Calibration.
1-31 Rotor Resistance (Rr)
Range:
Function:
NOTICE
Size
[ 0.0100 -
related
100.0000
*
Parameter 1-31 Rotor Resistance
Ohm]
(Rr) does not have effect when
parameter 1-10 Motor
Construction is set to [1] PM,
non-salient SPM.
MG06J202
Programming Guide
P 1-34
X'
P 1-35
P 1-31
X
R'
h
r
Danfoss A/S © 03/2019 All rights reserved.
1-31 Rotor Resistance (Rr)
Range:
Function:
Set the rotor resistance value R
improve shaft performance using 1
of these methods:
1-33 Stator Leakage Reactance (X1)
Range:
Function:
NOTICE
Size
[ 0.0400 -
related
400.0000
*
This parameter is only relevant
Ohm]
for asynchronous motors.
Set the stator leakage reactance of
the motor using 1 of these
methods:
See Illustration 4.5.
NOTICE
The parameter value is
updated after each torque
calibration if option [3] 1st
start with store or option [4]
Every start with store is
selected in
parameter 1-47 Torque
Calibration.
to
r
Run an AMA on a cold
motor. The frequency
converter measures the
value from the motor. All
compensations are reset
to 100%.
Enter the R
value
r
manually. Obtain the value
from the motor supplier.
Use the R
default setting.
r
The frequency converter
establishes the setting
based on the motor
nameplate data.
Run an AMA on a cold
motor. The frequency
converter measures the
value from the motor.
Enter the X
value
1
manually. Obtain the value
from the motor supplier.
Use the X
default setting.
1
The frequency converter
establishes the setting
based on the motor
nameplate data.
37
4
4