Danfoss VLT AutomationDrive FC 361 Programming Manual page 140

90–315 kw, enclosure sizes j8–j9
Hide thumbs Also See for VLT AutomationDrive FC 361:
Table of Contents

Advertisement

Parameter Descriptions
14-90 Fault Level
This is an array parameter with 26 elements. Each of the bits can
be configured to any of the following options. Use this
parameter to customize fault levels.
Option:
[2]
Trip
4
4
[3]
Trip Lock
Failure
10 V low
24 V low
1.8 V supply low
Voltage limit
Ground fault during ramping
Ground fault 2 during cont.
operation
Torque limit
Overcurrent
Short circuit
Heat sink temperature
Heat sink sensor
Control card temperature
Power card temperature
Heat sink temperature
Heat sink sensor
Power card temperature
Motor phase missing
Locked rotor
Table 4.18 Selection of Action when Selected Alarm Appears
MCT 10 Set-up Software has the element numbers listed in the column ID. Use this table together with MCT 10 Set-up Software to get information
about specific fault levels.
D stands for the default setting.
X stands for a possible option.
138
VLT® AutomationDrive FC 361
Function:
Changing a fault level from default
option [3] Trip Lock to [2] Trip leads
to the automatic reset of the alarm.
For alarms involving overcurrent,
the frequency converter has a
hardware protection that issues a 3-
minute recovery after 2 consecutive
overcurrent incidents. This hardware
protection cannot be overruled.
Alarm
Element in
parameter 14-90 Fau
lt Level
1
1490.0
47
1490.1
48
1490.2
64
1490.3
14
1490.4
45
1490.5
12
1490.6
13
1490.7
16
1490.8
29
1490.9
39
1490.10
65
1490.11
69
1490.12
244
1490.13
245
1490.14
247
1490.15
30–32
1490.16
99
1490.20
Danfoss A/S © 03/2019 All rights reserved.
14-90 Fault Level
This is an array parameter with 26 elements. Each of the bits can
be configured to any of the following options. Use this
parameter to customize fault levels.
Option:
Function:
[4]
Trip w.
This option adds a delay between
delayed reset
automatic resets, otherwise it is the
same as option [2] Trip. The delay
prevents a situation where reset is
attempted repeatedly for an
overcurrent situation. Hardware
protection of the frequency
converter forces the 3-minute
recovery time after 2 consecutive
overcurrents (within a short time
window).
Off
Warning
Trip
X
D
X
X
X
D
D
D
X
D
X
X
X
X
X
X
X
X
X
X
D
Trip Lock
Trip with
delayed
reset
D
D
X
X
D
D
D
D
D
D
D
D
D
D
X
MG06J202