Parameter Descriptions
3-12 Catch up/slow Down Value
Range:
0 %
*
4
4
3-13 Reference Site
Option:
[0]
Linked to
*
Hand / Auto
[1]
Remote
[2]
Local
3-14 Preset Relative Reference
Range:
0 %
*
200 %]
52
Function:
[0 - 100 %]
Enter a percentage (relative) value
to be either added to or deducted
from the actual reference for catch
up or slow down. If catch up is
selected via 1 of the digital inputs
(parameter 5-10 Terminal 18 Digital
Input to parameter 5-15 Terminal 33
Digital Input), the percentage
(relative) value is added to the total
reference. If slow down is selected
via 1 of the digital inputs
(parameter 5-10 Terminal 18 Digital
Input to parameter 5-15 Terminal 33
Digital Input), the percentage
(relative) value is deducted from
the total reference. Obtain
extended functionality with the
DigiPot function. See parameter
group 3-9* Digital Potentiometer.
Function:
Select which reference site to activate.
Use local reference when in hand-on mode,
or remote reference when in auto-on mode.
Use remote reference in both hand-on mode
and auto-on mode.
Use local reference in both hand-on mode
and auto-on mode.
NOTICE
When set to [2] Local, the frequency
converter starts with this setting again
after a power-down.
Function:
[-200 -
The actual reference, X, is increased
or decreased with the percentage Y,
set in parameter 3-14 Preset Relative
Reference.
This results in the actual reference
Z. Actual reference (X) is the sum of
the inputs selected in:
Parameter 3-15 Reference 1
Source.
Parameter 3-16 Reference 2
Source.
Parameter 3-17 Reference 3
Source.
Parameter 8-02 Control
Source.
Danfoss A/S © 03/2019 All rights reserved.
VLT® AutomationDrive FC 361
Illustration 4.15 Preset Relative Reference
-100
Illustration 4.16 Actual Reference
3-15 Reference Resource 1
Option:
[0]
[1]
*
[2]
[7]
[8]
[11]
[20]
[21]
[22]
[30]
[32]
Y
Resulting
Relative
Z
actual
X
Z=X+X*Y/100
reference
Z
X
0
P 3-14
Function:
Select the reference input to be
st
used for the 1
Parameter 3-15 Reference Resource 1,
parameter 3-16 Reference Resource 2,
and parameter 3-17 Reference
Resource 3 define up to 3 different
reference signals. The sum of these
reference signals defines the actual
reference.
No function
Analog Input
53
Analog Input
54
Frequency
input 29
Frequency
input 33
Local bus
Reference from terminals 68 and 69.
reference
Digital
pot.meter
®
Analog input
VLT
General Purpose I/O MCB 101
X30/11
Analog input
®
VLT
General Purpose I/O MCB 101
X30/12
Option
Reference
Bus PCD
Y
100
%
reference signal.
MG06J202