Parameter Descriptions
3-16 Reference Resource 2
Option:
Function:
Select the reference input to be
used for the 2
Parameter 3-15 Reference Resource 1,
parameter 3-16 Reference Resource 2,
and parameter 3-17 Reference
Resource 3 define up to 3 different
reference signals. The sum of these
reference signals defines the actual
reference.
[0]
No function
[1]
Analog Input
53
[2]
Analog Input
54
[7]
Frequency
input 29
[8]
Frequency
input 33
[11]
Local bus
Reference from terminals 68 and 69.
reference
[20]
Digital
pot.meter
[21]
Analog input
X30/11
[22]
Analog input
X30/12
[32]
Bus PCD
3-17 Reference Resource 3
Option:
Function:
Select the reference input to be
used for the 3
Parameter 3-15 Reference Resource 1,
parameter 3-16 Reference Resource 2,
and parameter 3-17 Reference
Resource 3 define up to 3 different
reference signals. The sum of these
reference signals defines the actual
reference.
[0]
No function
[1]
Analog Input
53
[2]
Analog Input
54
[7]
Frequency
input 29
[8]
Frequency
input 33
[11]
Local bus
Reference from terminals 68 and 69.
reference
[20]
Digital
pot.meter
MG06J202
Programming Guide
3-17 Reference Resource 3
Option:
[21]
nd
reference signal.
[22]
[32]
3-18 Relative Scaling Reference Resource
Option:
rd
reference signal.
[0]
*
[1]
[2]
[7]
[8]
[11]
[20]
[21]
[22]
[32]
Danfoss A/S © 03/2019 All rights reserved.
Function:
Analog input
X30/11
Analog input
X30/12
Bus PCD
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Select a variable value to be added
to the fixed value (defined in
parameter 3-14 Preset Relative
Reference). The sum of the fixed
and variable values (labeled Y in
Illustration 4.17) is multiplied by the
actual reference (labeled X in
Illustration 4.17). This product is
then added to the actual reference
(X+X*Y/100) to give the resulting
actual reference.
Y
Relative
X
Z=X+X*Y/100
Illustration 4.17 Resulting Actual
Reference
No function
Analog Input
53
Analog Input
54
Frequency
input 29
Frequency
input 33
Local bus
Reference from terminals 68 and 69.
reference
Digital
pot.meter
Analog input
X30/11
Analog input
X30/12
Bus PCD
4
4
Resulting
Z
actual
reference
53