Output Signal - Mitsubishi Electric MELSERVO-J4 Series Instruction Manual

Cc-link ie field network interface servo amplifier instruction manual (motion mode)
Hide thumbs Also See for MELSERVO-J4 Series:
Table of Contents

Advertisement

Device
Warning
Battery warning
Variable gain selection
Absolute position
undetermined
During tough drive
During fully closed loop
control

Output signal

Signal name
Encoder A-phase pulse
(differential line driver)
Encoder B-phase pulse
(differential line driver)
Encoder Z-phase pulse
(differential line driver)
Analog monitor 1
Analog monitor 2
Power supply
Signal name
Digital I/F power supply
input
Digital I/F common
Monitor common
Shield
3 SIGNALS AND WIRING
108
3.5 Signal (device) explanations
Symbol
Function and application
WNG
When warning has occurred, WNG turns on. When a warning is not occurring, turning on the power will turn off
WNG after 2.5 s to 3.5 s.
BWNG
BWNG turns on when [AL. 92 Battery cable disconnection warning] or [AL. 9F Battery warning] has occurred.
When the battery warning is not occurring, turning on the power will turn off BWNG after 2.5 s to 3.5 s.
CDPS
CDPS will turn on during variable gain.
ABSV
ABSV turns on when the absolute position is undetermined.
The device cannot be used in the velocity mode and torque mode.
MTTR
When a tough drive is enabled in [Pr. PA20], activating the instantaneous power failure tough drive will turn on
MTTR.
CLDS
CLDS turns on during fully closed loop control.
This is used with servo amplifiers with software version A1 or later.
Symbol
Connector
Function and application
pin No.
LA
CN3-6
These devices output pulses of encoder output set in [Pr. PA15] and [Pr. PA16] in the differential line
LAR
CN3-16
driver type.
In CCW rotation of the servo motor, the encoder B-phase pulse lags the encoder A-phase pulse by a
phase angle of /2.
LB
CN3-7
The relation between rotation direction and phase difference of the A-phase and B-phase pulses can
LBR
CN3-17
be changed with [Pr. PC03].
Output pulse specification, dividing ratio setting, and electronic gear setting can be selected.
LZ
CN3-8
The encoder zero-point signal is output in the differential line driver type. One pulse is output per servo
LZR
CN3-18
motor revolution. This turns on when the zero-point position is reached. (negative logic)
The minimum pulse width is about 400 s. For home position return using this pulse, set the creep
speed to 100 r/min or less.
MO1
CN3-4
This is used to output the data set in [Pr. PC09] to between MO1 and LG in terms of voltage.
Resolution: 10 bits or equivalent
MO2
CN3-14
This signal outputs the data set in [Pr. PC10] to between MO2 and LG in terms of voltage.
Resolution: 10 bits or equivalent
Symbol
Connector
Function and application
pin No.
Input 24 V DC (24 V DC  10% 300 mA) for I/O interface. The power supply capacity changes
DICOM
CN3-5
depending on the number of I/O interface points to be used.
For sink interface, connect + of 24 V DC external power supply.
For source interface, connect - of 24 V DC external power supply.
DOCOM
CN3-3
Common terminal of input signal such as EM2 of the servo amplifier. This is separated from LG.
For sink interface, connect - of 24 V DC external power supply.
For source interface, connect + of 24 V DC external power supply.
LG
CN3-11
Common terminal of MO1 and MO2.
SD
Plate
Connect the external conductor of the shielded wire.