• Selection example of MCCB and fuse
Use T class fuses or molded-case circuit breaker (UL 489 Listed MCCB) as the following table. The T class fuses and
molded-case circuit breakers in the table are selected examples based on rated I/O of the servo amplifiers. When you select
a smaller capacity servo motor to connect it to the servo amplifier, you can also use smaller capacity T class fuses or molded-
case circuit breaker than ones in the table. For selecting ones other than Class T fuses and molded-case circuit breakers
below and selecting a Type E Combination motor controller, refer to the following.
Page 404 Molded-case circuit breakers, fuses, magnetic contactors
Servo amplifier (100 V class)
MR-J4-10_1/MR-J4-20_1/MR-J4-40_1
Servo amplifier (200 V class)
MR-J4-10_/MR-J4-20_/MR-J4-40_/MR-J4-60_ (T)/
MR-J4-70_ (T)/MR-J4W2-22B (T)
MR-J4-60_ (S)/MR-J4-70_ (S) /MR-J4-100_ (T)/
MR-J4W2-22B (S)/MR-J4W2-44B (T)/MR-J4W2-77B (T)/
MR-J4W3-222B/MR-J4W3-444B (T)
MR-J4-100_ (S)/MR-J4-200_ (T)/MR-J4W2-44B (S)/
MR-J4W2-1010B
MR-J4-200_ (S)/MR-J4-350_/MR-J4W2-77B (S)/
MR-J4W3-444B (S)
MR-J4-500_
MR-J4-700_
MR-J4-11K_
MR-J4-15K_
MR-J4-22K_
*1 "(S)" means 1-phase 200 V AC power input and "(T)" means 3-phase 200 V AC power input in the table.
Servo amplifier (400 V class)
MR-J4-60_4/MR-J4-100_4
MR-J4-200_4
MR-J4-350_4
MR-J4-500_4
MR-J4-700_4
MR-J4-11K_4
MR-J4-15K_4
MR-J4-22K_4
• Power supply
This servo amplifier can be supplied from star-connected supply with grounded neutral point of overvoltage category 
(overvoltage category  for 1-phase servo amplifiers, MR-J4-03A6, and MR-J4W2-0303B6) set forth in IEC/EN 60664-1. For
the interface power supply, use an external 24 V DC power supply with reinforced insulation on I/O terminals.
In case of MR-J4-03A6 and MR-J4W2-0303B6, use DC power supplies of reinforced insulation type. For the main circuit
power, use UL listed (recognized) 48 V DC/24 V DC power supplies which can generate more than 1.2 A/2.4 A per axis.
APPX
574
Appendix 4 Compliance with global standards
Molded-case circuit breaker (120 V AC)
NV50-SVFU-15A (50 A frame 15 A)
*1
Molded-case circuit breaker (240 V AC)
NF50-SVFU-5A (50 A frame 5 A)
NF50-SVFU-10A (50 A frame 10 A)
NF50-SVFU-15A (50 A frame 15 A)
NF50-SVFU-20A (50 A frame 20 A)
NF50-SVFU-30A (50 A frame 30 A)
NF50-SVFU-40A (50 A frame 40 A)
NF100-CVFU-60A (100 A frame 60 A)
NF100-CVFU-80A (100 A frame 80 A)
NF225-CWU-125A (225 A frame 125 A)
Molded-case circuit breaker (480 V AC)
NF100-HRU-5A (100 A frame 5 A)
NF100-HRU-10A (100 A frame 10 A)
NF100-HRU-10A (100 A frame 10 A)
NF100-HRU-15A (100 A frame 15 A)
NF100-HRU-20A (100 A frame 20 A)
NF100-HRU-30A (100 A frame 30 A)
NF100-HRU-40A (100 A frame 40 A)
NF100-HRU-60A (100 A frame 60 A)
Fuse (300 V)
20 A
Fuse (300 V)
10 A
15 A
30 A
40 A
60 A
80 A
125 A
150 A
300 A
Fuse (600 V)
10 A
15 A
20 A
30 A
40 A
60 A
80 A
125 A