■Cable clamp fitting AERSBAN-_SET
Generally, connecting the grounding of the shielded wire to the SD terminal of the connector provides a sufficient effect.
However, the effect can be increased when the shielded wire is connected directly to the grounding plate as shown below.
Install the grounding plate near the servo amplifier for the encoder cable. Peel part of the cable sheath to expose the external
conductor, and press that part against the grounding plate with the cable clamp. If the cable is thin, clamp several cables in a
bunch.
The cable clamp comes as a set with the grounding plate.
Cable clamp
(A, B)
External conductor
Clamp section diagram
• Dimensions
Earth plate
2- 5 hole
installation hole
6
*1
M4 screw
*1 Screw hole for grounding. Connect it to the grounding plate of the cabinet.
Model
AERSBAN-DSET
AERSBAN-ESET
Clamp fitting
A
B
[Unit: mm]
Cable
Earth plate
17.5
22
35
A
B
100
86
70
56
L
70
45
Strip the cable sheath of
the clamped area.
[Unit: mm]
Clamp section diagram
L or less
10
C
30