Input Mode (Characteristics) Bfm#0 - Mitsubishi Electric MELSEC-FX3S Series Manual

Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
FX
-4AD/FX
-4AD (4-channel Analog Input)
3U
3UC
2.4

Input Mode (Characteristics) BFM#0

For the 4AD, there are two types of input characteristics: voltage (-10 to +10V) and current (4 to 20mA, -20 to
+20mA) input characteristics. The input characteristics depend on the set input mode as described below. For
each input range, there are 3 input modes.
1. Voltage input characteristics [-10 to +10V] (Input mode: 0 to 2)
Set input mode: 0
Input type: Voltage input
Analog input range: -10 to +10V
Digital output range: -32000 to +32000
Offset/gain adjustment: Possible
Digital value
+32640
+32000
Input
voltage
-10V
2. Current input characteristics [4 to 20mA] (Input mode: 3 to 5)
Set input mode: 3
Input type: Current input
Analog input range: 4 to 20 mA
Digital output range: 0 to 16000
Offset/gain adjustment: Possible
Digital value
16400
16000
0
4mA
3. Current input characteristics [-20 to +20mA] (Input mode: 6 to 8)
Set input mode: 6
Input type: Current input
Analog input range: -20 to +20 mA
Digital output range: -16000 to +16000
Offset/gain adjustment: Possible
Digital value
+16320
+16000
Current
-20mA
Input
B-8
PLC User's Manual - Analog Control Edition
3UC
Set input mode: 1
Input type: Voltage input
Analog input range: -10 to +10V
Digital output range: -4000 to +4000
Offset/gain adjustment: Possible
Input
0
voltage
+10V
-32000
-32640
Set input mode: 4
Input type: Current input
Analog input range: 4 to 20 mA
Digital output range: 0 to 4000
Offset/gain adjustment: Possible
Digital value
4100
4000
Current
20mA
input
Set input mode: 7
Input type: Current input
Analog input range: -20 to +20 mA
Digital output range: -4000 to +4000
Offset/gain adjustment: Possible
Current
0
Input
+20mA
-16000
-16320
Digital value
+4080
+4000
-10V
0
+10V
-4000
-4080
4mA
Current
0
20mA
input
Digital value
+4080
+4000
-20mA
0
+20mA
-4000
-4080
2 Specifications
2.4 Input Mode (Characteristics) BFM#0
Set input mode: 2
Input type: Voltage input
(analog value direct indication)
Analog input range: -10 to +10V
Digital output range: -10000 to +10000
Offset/gain adjustment: Impossible
Digital value
+10200
+10000
Input
voltage
-10V
0
+10V
-10000
-10200
Set input mode: 5
Input type: Current input
(analog value direct indication)
Analog input range: 4 to 20 mA
Digital output range: 4000 to 20000
Offset/gain adjustment: Impossible
Digital value
20400
20000
4000
4mA
0
20mA
Set input mode: 8
Input type: Current input
(analog value direct indication)
Analog input range: -20 to +20 mA
Digital output range: -20000 to +20000
Offset/gain adjustment: Impossible
Digital value
+20400
+20000
Current
-20mA
0
Input
+20mA
-20000
-20400
Current
input

Advertisement