Calibration Initialization; Calibration Completion - Qualstar RLS-4470 Technical & Service Manual

Tape library; rls-4000 series; rls-5000 series; rls-6000 series; rls-8000 series;
Table of Contents

Advertisement

7.24.2 Calibration Initialization

Apply power to the RLS.
The RLS must have been given a "
Menu to appear. If the Private Menu is not included in the Top Menu, follow the in-
structions in Section 5.3.2 to set the "
Initiate the Calibration Command as described in Section 5.4.1.
The Carousel or Storage Array and the Handler will all move from time to time. It
will display a series of status messages as the calibration process progresses.

7.24.3 Calibration Completion

If the calibration completed without a problem, the RLS illuminates the green
READY (LED) and no messages are displayed. If you're all done for the day, clear the
password as described in Section 5.3.3.
If the RLS failed to calibrate properly, then an error message indicating the possible
reason for the failure will be displayed and the red FAULT LED will illuminate.
Remedy the reason for failure and repeat the Calibrate command.
7-74
Service
Service
Field–Replaceable Units (FRUs)
" or "
" password for the Private
Update
" or "
" passwords.
Update
501510 Rev. S